User Manual
Version 1.31 July 2010
HRT-710 HRT-310
Written by Peter Ho
Edited by Julia Wang
Page 1: ...User Manual Version 1 31 July 2010 HRT 710 HRT 310 Written by Peter Ho Edited by Julia Wang...
Page 2: ...19 2 5 1 The default values in the Default mode 20 2 6 Jumper 21 2 7 Module Loop Power Wiring HRT 310 22 3 HART Introduction 23 3 1 Analog and Digital signal 23 3 2 Network topology 24 3 3 HART Frame...
Page 3: ...t Translation 66 5 3 4 9About 67 5 4 Establish connection with module 68 6 Troubleshooting 71 7 Dimensions 72 8 FAQ 76 Q01 How to add HART devices to HRT 710 76 Q02 How to make sure that HRT 710 gets...
Page 4: ...dd the HART Device Specific command to HRT 710 115 Q12 How to set HART device address by HRT 710 utility 118 Q13 All kinds of HART network wiring 121 Q14 Apply the same settings to the other HRT 710 r...
Page 5: ...liable However no responsibility is assumed by ICP DAS for its use not for any infringements of patents or other rights of third parties resulting from its use Copyright Copyright 2017 by ICP DAS Co L...
Page 6: ...ation of HRT 710 HRT 310 The below table are the difference between HRT 710 and HRT 310 HRT 710 HRT 310 Din Rail Installation Horizontal Upright HART Signal Standard Enhanced send receive signal For l...
Page 7: ...firmware update via Com Port FW_v1 2 and HW_v1 2 Support on line replacement of HART devices FW_v1 5 Support acquire long frame address automatically FW_v1 5 Isolated COM 1 RS 232 422 485 Provide LED...
Page 8: ...sters 1 3 Specifications UART Spec COM RS 232 3 wire RS 422 RS 485 HRT 710 Connector 9 pin screwed terminal block HRT 310 Connector 4 pin screwed terminal block Baud Rate 1200 115200 bps Data Format 1...
Page 9: ...m x 121 mm x 35 mm W x L x H HRT 310 Dimensions 25 mm x 116 mm x 120 mm W x L x H Operating temperature 25 75 C Storage temperature 30 80 C Humidity 5 95 RH non condensing LED Status Indicators Table...
Page 10: ...lock Diagram Figure 2 Block diagram 2 2 Pin Assignment Figure 3 1 Pin assignment of HRT 710 HRT 710 HRT 310 User Manual Version 1 31 Page 10 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail se...
Page 11: ...Top View Bottom View Figure 3 2 Pin assignment of HRT 310 HRT 710 HRT 310 User Manual Version 1 31 Page 11 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail service icpdas com...
Page 12: ...of Power Supply RXD 11 18 Receive Data of RS 232 TXD 12 17 Transmit Data of RS 232 GND 13 19 GND of RS 232 RX 14 15 Receive Data of RS 422 RX 15 16 Receive Data of RS 422 TX 16 13 Transmit Data of RS...
Page 13: ...dbus network 2 3 1 RS 232 Wiring The RS 232 port of the HRT 7 3 10 has only three pins The wiring of the RS 232 device with the RS 232 port of the HRT 7 3 10 is shown as Figure 4 Figure 4 RS 232 wirin...
Page 14: ...RT Wiring The HART bus wiring is divided into the below two types 1 Point to Point mode 2 Multi drop mode Fig 2 3 4 1 P2P mode Two wired HART device Module Internal Resistor HRT 710 HRT 310 User Manua...
Page 15: ...mode Two wired HART device External Resistor Fig 2 3 4 3 P2P mode Four wired HART device HRT 710 HRT 310 User Manual Version 1 31 Page 15 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail serv...
Page 16: ...ulti drop mode Two wired HART device Fig 2 3 4 5 Multi drop mode Four wired HART device HRT 710 HRT 310 User Manual Version 1 31 Page 16 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail servic...
Page 17: ...Fig 2 3 4 6 Multi drop mode Two wired and Four wired HART device HRT 710 HRT 310 User Manual Version 1 31 Page 17 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail service icpdas com...
Page 18: ...ly Failed Flash HART Comm Error ERR OFF HART Comm OK Flash Flash per second Module in initial mode Flash per half second Module received the burst frame from HART device ON Module in normal operation...
Page 19: ...fer to section 2 5 1 of HRT 710 will be adapted Figure 12 1 DIP Switch of the HRT 710 2 HRT 310 There are 4 dip switches on the HRT 310 and these functions are as below Item OFF ON Loop PWR Adapt the...
Page 20: ...T Cmd timeout value 1000 ms Auto Polling Enabled Retry count 3 Modbus Default Value Item Value Baud rate 115200 bps Date bits 8 bits Stop bits 1 bit Parity None Net ID Modbus ID 1 Protocol Modbus RTU...
Page 21: ...ill connect to HART bus When the pin 2 3 of JP4 is closed or JP4 without jumper connected it will disconnect the resistor from HART bus By default the pin1 2 of JP4 is closed Please refer to section 2...
Page 22: ...the HART pin of HART device 2 Connect the H of HRT 310 to the HART pin of HART device 3 Turn the dip switch of Loop Power in HRT 310 to ON position It will connect the H of HRT 310 to the internal LP...
Page 23: ...e up of two frequencies 1 200 Hz and 2 200 Hz representing bits 1 and 0 respectively Sine waves of these two frequencies are superimposed on the direct current dc analog signal cables to provide simul...
Page 24: ...itally The polling address of all field devices must be bigger than 0 and between 1 15 The current through each device is fixed to a minimum value typically 4 mA The maximum HART device number in HART...
Page 25: ...Figure 17 Multi drop topology HRT 710 HRT 310 User Manual Version 1 31 Page 25 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail service icpdas com...
Page 26: ...e is master frame slave frame or burst frame 3 3 3 Address If the HART frame is short frame the address field is only one byte If it is long frame the address field is 5 bytes and include manufacturer...
Page 27: ...ems and Field device status They are shown as below First Byte bit 7 1 communication error bit 6 Parity error bit 5 Overrun error bit 4 Framing error bit 3 Checksum error bit 2 0 reserved bit 1 Rx buf...
Page 28: ...Analog output saturated bit 1 Non primary variable out of limits bit 0 Primary variable out of limits Note When HART communication error is reported in the first byte the second byte will be 0 3 3 7 D...
Page 29: ...e all initial commands and the RUN LED will flash 2 When HRT 7 3 10 runs under Operation mode it will execute all polling commands automatically and the RUN LED will be always on Note The Auto Polling...
Page 30: ...Description User CMD Data 0 1F3 0 499 User CMD data Module State Data 1F4 500L Module state machine 1F4 500H Module request command count 1F5 501L Module receive command count 1F5 501H Module receive...
Page 31: ...put data of Module 15 Default CMD 3 N Data 26A 276 618 630 Default CMD 3 N data of Module 0 277 283 631 643 Default CMD 3 N data of Module 1 284 290 644 656 Default CMD 3 N data of Module 2 291 29D 65...
Page 32: ...odule 5 3EE 1006 Default CMD 0 3 status of Module 6 3EF 1007 Default CMD 0 3 status of Module 7 3F0 1008 Default CMD 0 3 status of Module 8 3F1 1009 Default CMD 0 3 status of Module 9 3F2 1010 Default...
Page 33: ...329 Default CMD 3 S data of Module 2 532 53B 1330 1339 Default CMD 3 S data of Module 3 53C 545 1340 1349 Default CMD 3 S data of Module 4 546 54F 1350 1359 Default CMD 3 S data of Module 5 550 559 13...
Page 34: ...D Module DEV Device 2 500L The low byte of MB_Addr 500 500H The high byte of MB_Addr 500 3 Default CMD num format 1 Num means HART command number When add a new HART device in module these two default...
Page 35: ...r of HART data has some error 5 The address the bit of master type of HART data has some error 6 The address the bit of burst mode of HART data has some error 7 The command of HART data has some error...
Page 36: ...will refer to the index value 0 99 255 is for through mode of trigger command to execute the corresponding user command Ex If the index of trigger command is 0 and the output trigger function value is...
Page 37: ...shown as below Input Data Area Description 500 502 Module state data 826 883 Module error record data 1000 1015 Default CMD 0 3 status data 1050 1099 User CMD 0 99 error status HRT 710 HRT 310 User M...
Page 38: ...and error count from Error count in through mode MB 1151L Step 7 Change the Output Trigger function value MB 502L Step 8 Get the value of Receive count in through mode and Error count in through mode...
Page 39: ...e backplane of HRT 710 to the default position 2 HRT 310 Set the Default dip switch to be ON position Please reboot the module and the default settings are as below Item Value Baud rate 115200 bps Dat...
Page 40: ...6 Word 4 0x1B Byte 9 0x10 Byte 8 Word 5 0x1B Byte 11 0x00 Byte 10 Word 6 0xE8 Byte 13 0x97 Byte 12 The HART command 0 format is 2 bytes response code and 12 bytes data Response code1 Byte 0 0x00 mean...
Page 41: ...dware revision Byte 10 0x00 Flags Byte 11 13 0x1B 0x97 0xE8 Device ID number Figure 23 Modbus RTU send and receive data HRT 710 HRT 310 User Manual Version 1 31 Page 41 Copyright 2017 ICP DAS Co Ltd A...
Page 42: ...ID 0856eacb 4362 4b0d 8edd aab 15c5e04f5 DisplayLang en Microsoft Net Framework Version 3 5 http www microsoft com downloads details aspx familyid 333325FD AE52 4E35 B531 508 D977D32A6 displaylang en...
Page 43: ...Step2 After finishing the installation press Finish button to exit Figure 26 Install NET Framework Step3 HRT 710 HRT 310 User Manual Version 1 31 Page 43 Copyright 2017 ICP DAS Co Ltd All Rights Rese...
Page 44: ...gateway utilities hg_tool Step 2 Execute the Setup exe file to install the HG_Tool Utility Figure 27 Install the utility Step 3 Click the Next button to continue If you want to change the installation...
Page 45: ...utton to confirm installation Figure 29 Confirm installation Step 5 Click the Close button to finish and exit the installation program HRT 710 HRT 310 User Manual Version 1 31 Page 45 Copyright 2017 I...
Page 46: ...ng the installation of the HG_Tool users can find the utility as shown in the following screen shot Figure 31 The path of HG_Tool HRT 710 HRT 310 User Manual Version 1 31 Page 46 Copyright 2017 ICP DA...
Page 47: ...Status 3 Connection Control 4 Tools 5 3 1 Traffic Light 1 The com port of PC has not be opened yet 2 The com port of PC is open and try to connect to HRT 7 3 10 3 The PC connect to HRT 7 3 10 success...
Page 48: ...port 5 3 4 Tools The HG_Tool includes 9 parts as below 1 Communication Settings 2 Device Information 3 Device Configuration 4 Default Output Data 5 Address Map 6 Device Diagnostic 7 Through Mode 8 For...
Page 49: ...ll show the item data in the right side About the data of these items is shown as Table 6 Table 6 The data of the node Node Behavior Data HRT 710 click Module name HRT 710 HRT 310 Firmware version V01...
Page 50: ...t to Point Multi drop Preamble length 5 20 Master type Primary Secondary Master Frame type Short Long Frame Module address 0 15 Auto Get Unique ID Enable Disable Manufacturer ID 1 byte Device type 1 b...
Page 51: ...options 1 Basic Operation Read Write the User CMD data by using window option 2 Advanced Operation Read Write the User CMD data by using address mapping 1 The Basic Operation of System item Figure 35...
Page 52: ...Request Count 0 255 It will show the request count of HART UserCmd 3 Response Count 0 255 It will show the response count of HART UserCmd 4 Error Count 0 255 It will show the response error count of...
Page 53: ...it will update the data from HRT 7 3 10 MB_Addr 500 502 in Input Data Area 3 The Basic Operation of Default User CMD item In the function only supports HART command 0 1 2 3 6 11 12 13 14 15 16 17 18 1...
Page 54: ...ation 2 Update button When click the button it will update the input and output data from HRT 7 3 10 module 4 The Advanced Operation of Default User CMD item Users can read write HART command data via...
Page 55: ...click the button it will send the output data to HRT 7 3 10 2 Update button When click this button it will update the input and output data from HRT 7 3 10 HRT 710 HRT 310 User Manual Version 1 31 Pag...
Page 56: ...window The following is detailed description Table 6 The data of the node Node Behavior Data HRT 710 click Module name Firmware version System click Module name System System Module count 0 16 Comman...
Page 57: ...Edit Configure the Modbus and HART comm settings of HRT 7 3 10 2 Add Module Add new HART device in HRT 7 3 10 Module click Module name Module Channel 0 Auto Configuration Enable Disable Network Point...
Page 58: ...num 0 255 Command mode Initial Polling Command format Normal Simple Command in size 2 255 Command out size 0 255 Command in address Command out address User CMD click Module name User CMD Module index...
Page 59: ...ount 0 5 When HART comm error happened HRT 710 will re send the HART Cmd for Retry count times 5 The following are the Com Port comm setting of HRT 7 3 10 1 Baud Rate 1200 115200 bps 2 Data Bits 7 or...
Page 60: ...s manufacturer ID device type and device ID of HART device automatically Note If enables this function just supports HART Point to Point mode 3 Frame type Short or Long frame 4 Master type Primary or...
Page 61: ...l not execute the default HART Cmd Initial module will execute the default HART Cmd automatically when in Initial mode Polling module will execute the default HART Cmd automatically when in Operation...
Page 62: ...f HART command Ex HART Cmd 0 2 response code 12 14 5 Out Size Set the output data length of HART command Ex HART command 0 0 HART command 6 1 5 3 4 4 Default Output Data Figure 43 The window of defaul...
Page 63: ...able 2 The data of Modbus AI table can be read by MB Function Code 4 3 The data of Modbus AO table can be read by MB Function Code 3 and written by MB Function Code 6 or 16 Note The MB address of the...
Page 64: ...een executed 3 It means the command has error and the error status shows at the right side of the window 4 It means the item is selected 2 Status Update button Refresh the status of HART Cmd 3 Record...
Page 65: ...0x00 0x00 and then click Send button to send HART Cmd 2 Click Update button to show the response of HART device Warning Before using through mode function please check the below items 1 The RUN LED i...
Page 66: ...convert IEEE754 into byte format 1 Packed ASCII Translate It can be used to convert between Packed ASCII and ASCII format Figure 48 The window of packed ASCII translate 2 IEEE 754 Translate It can be...
Page 67: ...5 3 4 9 About Figure 50 The window of About HRT 710 HRT 310 User Manual Version 1 31 Page 67 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail service icpdas com...
Page 68: ...re COM Port of PC to RS 232 port of HRT 7 3 10 Step 2 Run HG_Tool on PC Figure 52 Run HG_Tool Utility Step 3 Set COM Port comm setting of HG_Tool the same as HRT 7 3 10 The default settings of HRT 7 3...
Page 69: ...Port settings of the utility Step 4 Click Connect button Figure 54 Click Connect button HRT 710 HRT 310 User Manual Version 1 31 Page 69 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail servi...
Page 70: ...connection is successful then the traffic light shows green Figure 55 Connection status HRT 710 HRT 310 User Manual Version 1 31 Page 70 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail servi...
Page 71: ...k the wiring between HRT 7 3 10 and HART devices and the configuration of HRT 7 3 10 2 If the problem still exists please connect to only one HART device Then set the configuration of HRT 7 3 10 again...
Page 72: ...7 Dimensions HRT 710 HRT 710 HRT 310 User Manual Version 1 31 Page 72 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail service icpdas com...
Page 73: ...HRT 710 HRT 310 User Manual Version 1 31 Page 73 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail service icpdas com...
Page 74: ...HRT 310 HRT 710 HRT 310 User Manual Version 1 31 Page 74 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail service icpdas com...
Page 75: ...HRT 710 HRT 310 User Manual Version 1 31 Page 75 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail service icpdas com...
Page 76: ...th HG_Tool utility 1 Set the com port parameters 2 Click the Connect button to connect to HRT 710 module like Figure 1 1 Figure 1 1 Connect to HRT 710 Step 2 Delete the default HART device setting in...
Page 77: ...e Auto Configure option to be Enable like Figure 1 3 Figure 1 3 Add new HART device setting Auto Config Enable 2 Method 2 Choose Auto Configure option to be Disable like Figure 1 4 HRT 710 HRT 310 Use...
Page 78: ...ick the Save to Device button to save the new HART device setting to HRT 710 like Figure 1 5 Figure 1 5 Save to Device function 2 Add More than One HART devices Ex Add two HART devices HRT 710 HRT 310...
Page 79: ...nnect to HRT 710 with HG_Tool utility Step 2 Delete the default HART device setting in HRT 710 These above two steps are the same with those of the Only One HART device Step 3 Add two new HART device...
Page 80: ...ing to HRT 710 1 Click the Save to Device button to save the new HART device setting to HRT 710 like Figure 1 7 Figure 1 7 Save to Device function HRT 710 HRT 310 User Manual Version 1 31 Page 80 Copy...
Page 81: ...essfully and then click Device Information button like Figure 2 1 Figure 2 1 Device Information screen Check I O Data of the Default CMD 0 2 Right click the button of mouse on the Default CMD 0 item a...
Page 82: ...is NG like Figure 2 4 Figure 2 4 The I O Data screen of the Default CMD 0 NG Check I O Data of the Default CMD 3 5 Right click the button of mouse on the Default CMD 3 item and choose the Basic operat...
Page 83: ...The I O Data of the Default CMD 3 is NG like Figure 2 7 Figure 2 7 The I O Data screen of the Default CMD 3 NG If the I O data of the Default CMD 0 and Default CMD 3 is ok it means that the communicat...
Page 84: ...in HRT 710 to be W B 1 In Device Configuration screen right click the button of mouse on System item and click the Edit option to open System Edit screen like Figure 3 1 Figure 3 1 Open System Edit sc...
Page 85: ...save the new system setting to HRT 710 like Figure 3 3 Figure 3 3 Save to Device function 3 Check the firmware version of HRT 710 like Figure 3 4 HRT 710 HRT 310 User Manual Version 1 31 Page 85 Copy...
Page 86: ...Module 0 in HRT 710 the mapped MB address is 1300 1309 The below MB RTU client will use the ModScan and Modbus Poll tool to show the CMD 3 data of HART device by polling Modbus address 1300 1309 1 Con...
Page 87: ...5 The CMD 3 data of HART device is successfully read e g Figure 3 7 Figure 3 7 The CMD 3 data of HART device HRT 710 HRT 310 User Manual Version 1 31 Page 87 Copyright 2017 ICP DAS Co Ltd All Rights R...
Page 88: ...he Display Option within Setup menu after successful connected shown as Figure 3 8 Figure 3 8 The actual polling Modbus address 6 Check and modify Modbus Poll Address Base types and display formats li...
Page 89: ...elected for Modbus Poll If PLC Address Poll Base 1 has been selected instead then the address needs to be set as 1301 Users can make sure the actual polling address is 05 14 1300 by checking the Commu...
Page 90: ...click OK button to connect to HRT 710 like Figure 3 12 Figure 3 12 Com Port Parameters of Modbus Poll tool 9 The CMD 3 data of HART device is shown like Figure 3 13 HRT 710 HRT 310 User Manual Version...
Page 91: ...ve to Device to save the new HART device setting to HRT 710 like Figure 3 14 The mapped Modbus start address and length of User CMD 3 data can be found in Cmd In address and Cmd In size field In the e...
Page 92: ...w the CMD 3 data of HART device by polling Modbus address 0 9 1 Confirm the connection between HG_Tool and HRT 710 is disconnected 2 Set the Modbus parameters like Figure 3 15 HRT 710 HRT 310 User Man...
Page 93: ...format like Figure 3 16 Figure 3 16 Float format of Modbus Poll tool 4 Set the Com Port parameters and click OK button to connect to HRT 710 like Figure 3 17 HRT 710 HRT 310 User Manual Version 1 31...
Page 94: ...ure 3 18 Figure 3 18 The CMD 3 data of HART device 3 The below MB RTU client will use the ModScan tool to show the CMD 3 data of HART device by polling Modbus address 1300 1309 HRT 710 HRT 310 User Ma...
Page 95: ...oat 4th Variable The 30001 and 30002 registers mean Primary Variable Current 20 124636 The 30003 and 30004 registers mean Primary Variable 0 385210 The 30005 and 30006 registers mean Secondary Variabl...
Page 96: ...he newest firmware of HRT 710 Download from ftp ftp icpdas com pub cd fieldbus_cd hart gateway hrt 710 firmware 2 Turn off the power and open the shell of HRT 710 Then connect the pin 2 3 of JP5 toget...
Page 97: ...tool 1 Choose COM option and select Com Port number 2 Click Browser button to choose the firmware of HRT 710 3 Click Firmware Update button to start firmware update process 4 Wait for Firmware Update...
Page 98: ...together 6 Close the shell and turn on the power of HRT 710 Then users can check the firmware version of HRT 710 by using HG_Tool like Figure 4 5 Figure 4 5 Firmware Version of HRT 710 HRT 710 HRT 31...
Page 99: ...ave settings to HRT 710 The Modbus start address and length of the User CMD 1 will show in the Cmd In address and Cmd In size field like Figure 5 1 In the example they are 0 and 7 byte count 7 word co...
Page 100: ...Stop Bits Parity and then click Open button to connect to HRT 710 like Figure 5 2 4 Input 1 4 0 0 0 4 in Command field and click Send Command button to send the modbus command The HART command 1 data...
Page 101: ...database s byte and the order is low byte first For example Modbus register0 0x3412 database byte0 0x12 byte1 0x34 So we need to change the byte order So the data will be 00 00 0C 3E C5 20 A4 00 Accor...
Page 102: ...Unit code Byte 3 6 float Primary Variable So the data of HART command 1 is parsed as below Response code1 0x00 Response code2 0x00 Primary Variable Unit code 0x0C kPA Primary Variable 0x3E 0xC5 0x20...
Page 103: ...by ICP DAS to show HART command 1 data Download from http ftp icpdas com tw pub cd 8000cd napdos modbus modbus_utility 3 Run MB RTU tool Set the com port settings the same with HART 710 Baud Rate Dat...
Page 104: ...C5 C5 20 B0 B6 41 C0 78 42 39 91 C9 00 C5 00 00 00 00 Because the unit of HART 710 s database is byte and the unit of Modbus register is word and the Modbus register is composed of database s byte an...
Page 105: ...7 20 float Tertiary Variable So the data of HART command 3 is parsed as below Response code1 0x00 Response code2 0x00 Primary Variable Current 0x41 0xA1 0x01 0x22 20 125553 Primary Variable Unit code...
Page 106: ...of HART data has error 9 The communication with HART slave device has some error and The error messages are recorded in the responses codes Ex1 The Default CMD 3 of HART Device 0 1 in HRT 710 is Poll...
Page 107: ...device 0 2 Low Byte The comm status of Default CMD 3 in device 0 2 Address 1000 Unit WORD Show the comm status of Device 1 1 High Byte The comm status of Default CMD 0 in device 1 2 Low Byte The comm...
Page 108: ...the communication status of the User CMD Index 0 Figure 7 2 The status of the User CMD Index 0 1 In the Figure 7 2 the status of the User CMD Index 0 is 0x02 It means that the HART device for the User...
Page 109: ...below The method will be easy for users Default CMD 0 3 Status Data 3E8 1000 Default CMD 0 3 status of Device 0 3E9 1001 Default CMD 0 3 status of Device 1 3EA 1002 Default CMD 0 3 status of Device 2...
Page 110: ...different then the status address for HART devices will be also different The result will be as the below table Swap Type WORD swap disabled WORD swap enabled Modbus Start Addr From 999 From 1000 Fro...
Page 111: ...T 710 adjust JP4 to be pin2 and pin3 refer to the section 2 6 for detailed Then add the external resistor 250 Ohm 1W in HART network 2 The HART wiring of the Active and Passive HART devices please ref...
Page 112: ...to use 20 HRT 710 modules to connect to 20 HART devices with point to point wiring Software 1 Set the RS 485 station No Net ID of these twenty HRT 710 modules from 1 to 20 Please follow the below step...
Page 113: ...e Device Configuration please click the Save to Device button to save the parameters to HRT 710 Figure 9 3 Save the parameters to HRT 710 As a result these twenty HRT 710 modules can be integrated in...
Page 114: ...HRT 710 and I 7570 to do that and the wiring for this case is like figure 10 1 Figure 10 1 The Hardware Wiring for MCU900 Software Please refer to the steps in the Q01 Q02 and Q03 of HRT 710 FAQ to in...
Page 115: ...f Emerson 8800D is like Figure 11 1 Figure 11 1 The HART command No 149 format of Emerson 8800D 1 Add the HART command No 149 to HRT 710 like Figure 11 2 Figure 11 2 Add the HART command No 149 to HRT...
Page 116: ...bus address for data sending 2 In the Modbus AI area the light blue grid means the Modbus address for data receiving In the case the HART command No 149 is used for reading data Therefore the light bl...
Page 117: ...the Modbus Function Code 4 and address from 0 to 2 to get the HART command No 149 data Ex Request Cmd 0x01 0x04 0x00 0x00 0x00 0x03 HRT 710 HRT 310 User Manual Version 1 31 Page 117 Copyright 2017 IC...
Page 118: ...ge 3 Add UserCMD 6 and choose Manual option in Mode field Figure 12 1 4 Click Save to Device button Figure 12 2 Figure 12 1 Add UserCMD 6 Figure 12 2 Save to Device 2 Set HART device address and send...
Page 119: ...The Basic Operation of UserCMD 6 Figure 12 4 The I O Data screen of UserCMD 6 4 Right click on the System item and choose the Basic Operation 5 After finish the below settings click Send Data button t...
Page 120: ...a screen of System 3 Now the HART device address should be set to be 2 Then please reboot HRT 710 HRT 710 HRT 310 User Manual Version 1 31 Page 120 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E...
Page 121: ...The wiring of Point to Point Figure 13 1 HART_P2P_Network_Passive In Resistor Figure 13 2 HART_P2P_Network_Passive Ext Resistor HRT 710 HRT 310 User Manual Version 1 31 Page 121 Copyright 2017 ICP DAS...
Page 122: ...work_Active In Resistor 2 The wiring of Multi Drop Figure 13 4 HART_Multi Drop_Network_Passive jpg HRT 710 HRT 310 User Manual Version 1 31 Page 122 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E...
Page 123: ...5 HART_Multi Drop_Network_Active Figure 13 6 HART_Multi Drop_Network_Active Passive HRT 710 HRT 310 User Manual Version 1 31 Page 123 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail service i...
Page 124: ...utton to save the current settings of HRT 710 to file 2 Load the settings from HRT 710 file to the other HRT 710 module 1 In the Device Configuration click the Load From File button and choose the set...
Page 125: ...2 Click the Save to Device button to set the settings to HRT 710 module HRT 710 HRT 310 User Manual Version 1 31 Page 125 Copyright 2017 ICP DAS Co Ltd All Rights Reserved E mail service icpdas com...
Page 126: ...mouse on the HART Device 0 item and choose the Add Command option 2 Input the value 19 in the Command Num field and choose the Manual option in the Mode field Click the OK button to add the HART comma...
Page 127: ...1 10 00 00 00 02 04 21 00 0B 16 7F 6D 3 The below figure is the assigned value for writing in HART command 19 by using ModScan software for testing 4 After sending the above Modbus command users can c...
Page 128: ...for sending of UserCMD in the corresponding byte address in the Output Data area Users can see these values of 11 22 and 33 been set successfully 3 Trig the HRT 710 to send the UserCMD0 HART command 1...
Page 129: ...o send the UserCMD and it needs the different value every time Ex the next value will be 2 3 4 Now the UserCMD0 HART command 19 has been sent 2 Recover the original HART polling command The Modbus com...
Page 130: ...icpdas com root product solutions industrial_communication fieldbus hart co nverter hds html 2 The simulation value of HART Device 1 and 2 are as below table Current PV SV TV QV HART Dev1 4 00 11 1111...
Page 131: ...djustable Main Info RTU Mode Data Update Period sec 2 adjustable 2 Main Info Server Info Server IP The fixed IP address of PC that running RTU_Center software Main Info Server Info Server Port 10000 d...
Page 132: ...finish click the Write to Device button to save settings to GT 540 4 Run the M2M RTU Center software in the data center server 1 Create a new 3G connection device for the GT 540 1 Module choose the G...
Page 133: ...AI2 and AI3 DWORD 0x4131C717 Float 11 11111 3 SV AI4 and AI5 DWORD 0x41338E39 Float 11 22222 4 TV AI6 and AI7 DWORD 0x41355555 Float 11 33333 5 QV AI8 and AI9 DWORD 0x41371C71 Float 11 44444 3 Click t...
Page 134: ...he HART device data in HIM or SCADA There are two methods to get the data from M2M RTU_Center software Method 1 Using OPC Client InduSoft OPC Client Demo 1 Run the OPC Server M2M DA Server 2 Click the...
Page 135: ..._Center software 1 API Library Manual http ftp icpdas com pub cd usbcd napdos m2m rtu m2m_rtu_win32_api manual 2 API Library Demo http ftp icpdas com pub cd usbcd napdos m2m rtu m2m_rtu_win32_api soft...
Page 136: ...the request Byte 6 uint8 Command set revision number Byte 7 uint8 Transmitter specific revision code Byte 8 uint8 Software revision Byte 9 uint8 Hardware revision Byte 10 uint8 Flags Byte 11 13 uint24...
Page 137: ...Variable Current Byte 6 uint8 Primary Variable Unit code Byte 7 10 float Primary Variable Byte 11 uint8 Secondary Variable Unit code Byte 12 15 float Secondary Variable Byte 16 uint8 Tertiary Variable...
Page 138: ...s needed in the request Byte 6 uint8 Command set revision number Byte 7 uint8 Transmitter specific revision code Byte 8 uint8 Software revision Byte 9 uint8 Hardware revision Byte 10 uint8 Flags Byte...
Page 139: ...Response code 2 Byte 2 4 uint24 Sensor Serial Number MSB first Byte 5 uint8 Sensor limits unit Byte 6 9 float Upper sensor limit Byte 10 13 float Lower sensor limit Byte 14 17 float Minimum span Comm...
Page 140: ...se code 2 Byte 2 4 uint24 Final assembly number MSB first Command 17 Write Message Request data bytes 24 Index Format Description Byte 0 23 PA24 Message Response data bytes 2 24 26 Index Format Descri...
Page 141: ...and 19 Write Final Assembly Number Request data bytes 3 Index Format Description Byte 0 2 uint24 Final assembly number MSB first Response data bytes 2 3 5 Index Format Description Byte 0 uint8 Respons...
Page 142: ...le Request data bytes none Response data bytes 4 Index Format Description Byte 0 3 float Primary Variable 2 Command 2 Read P V Current and Percentage of Range Request data bytes none Response data byt...
Page 143: ...1 Add Simple Format function 1 23 Edward 2012 12 04 1 Modify the product name to HRT 710 2 FW update to v1 5 1 Add on line replacement of HART devices 2 Add Long Frame Address acquisition automatical...