Page 1: ...s valves from propane gas to natural gas Before the furnace can be operated with natural gas the low inlet pressure switch must be removed A gas valve conversion kit must be installed and main burner...
Page 2: ...any and all electrical wiring disconnected 6 Remove the four 4 screws holding the manifold and gas valve to the manifold supports Do not discard any screws 7 Carefully remove the manifold assembly an...
Page 3: ...derating of these furnaces at 2 Natural Gas and 4 Propane Gas has been tested and design certified by CSA t 1371 6m above sea level Use the 2001 to 3000 609 9 to 914 4m column in Table 1 Gas Valve Co...
Page 4: ...s per seconds per Sizeof test dial hour complete 05m3 kW m3 h rotation 3 600 80 05 2 25 3 600 80x 05 7 2 m3 h 2 25m3 hx 10 35 kWh m3 23 28 kW 23 28 x 3 412 79 431 BTU High Altitude Input Rate Nameplat...