![ICP N9MSB0401410B Service And Technical Support Manual Download Page 12](http://html1.mh-extra.com/html/icp/n9msb0401410b/n9msb0401410b_service-and-technical-support-manual_4159645012.webp)
SERVICE AND TECHNICAL SUPPORT MANUAL
Gas Furnace: N9MSB
Specifications subject to change without notice.
12
440 04 4412 01
h. Blower will run for 90 seconds before beginning the
call for heat again.
i. Furnace should ignite normally.
Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that the jumper is removed from the TEST/TWIN
terminal. Verify that there is nothing plugged into the PLT
connector.
NOTE
: If there is a jumper connector plugged into PLT, remove
it and discard. (See
3. Verify that the Blower/Heat Off Delay jumpers are set as
desired. (See
and
4. Verify that the blower (lower door in upflow position) and
control (“Main” or upper door in upflow position) doors
are properly installed.
5. Verify that the Status LED heartbeat (bright
−
dim). If not,
check that the power supply is energized and that the
blower door is secure. See
to interpret
diagnostic codes
.
6. Cycle test furnace with room thermostat to be sure that it
operates properly with the room thermostat. Check all
modes including Heat, Cool and Fan.
7. Check operation of accessories per manufacturer’s
instructions.
8. Review Home Owner’s Information with owner.
9. Attach entire literature packet to furnace.
Table 5
COOLING AIR DELIVERY - CFM (with filter
1
)
UNIT
SIZE
RETURN-AIR
CONNECTION
SPEED
TAPS
2
EXTERNAL STATIC PRESSURE (in.w.c.)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
0401410
SIDE/BOTTOM
Black
1160
1120
1070
1020
965
905
835
765
695
630
Blue
970
940
905
865
825
770
715
655
585
515
Yellow
920
890
855
820
770
720
665
600
545
465
Red
730
705
670
630
580
535
495
445
380
335
0401712
SIDE/BOTTOM
Black
1310
1255
1205
1150
1100
1045
985
930
870
805
Yellow
1215
1165
1120
1070
1025
970
915
860
800
740
Orange
1065
1030
1000
960
920
875
830
780
725
670
Blue
1005
980
950
920
880
840
790
745
695
640
Red
750
740
720
700
670
640
615
585
550
500
0601412
SIDE/BOTTOM
Black
1295
1265
1230
1195
1155
1110
1055
990
895
795
Blue
1035
1010
980
940
905
865
805
740
655
580
Yellow
965
940
915
885
855
805
750
685
610
530
Red
5
760
735
705
675
630
570
520
470
405
335
0601716
SIDE/BOTTOM
Black
1760
1705
1635
1575
1505
1430
1355
1270
1180
1090
Yellow
1415
1400
1365
1335
1290
1240
1180
1115
1040
965
Orange
1065
1060
1050
1035
1010
975
940
890
835
770
Blue
1010
1000
990
975
955
925
885
845
785
720
Red
770
745
730
710
685
660
625
585
545
500
0801716
SIDE/BOTTOM
Black
1800
1770
1735
1685
1630
1570
1495
1415
1330
1230
Yellow
1445
1430
1410
1385
1350
1305
1255
1195
1120
1045
Orange
1250
1240
1225
1200
1170
1130
1090
1040
975
910
Blue
1090
1080
1060
1035
1010
970
930
885
835
765
Red
5
880
860
835
810
780
750
710
665
615
560
0802120
BOTTOM or
TWO-SIDES
3,4
Black
2310
2235
2140
2050
1960
1860
1755
1650
1535
1430
Yellow
1720
1700
1670
1625
1570
1505
1435
1360
1275
1185
Orange
1515
1500
1480
1445
1405
1350
1290
1225
1155
1075
Blue
1150
1135
1105
1080
1050
1020
980
935
880
815
Red
945
915
885
860
835
805
770
720
670
610
1002116
SIDE/BOTTOM
Black
1725
1700
1665
1620
1570
1510
1445
1365
1265
1160
Blue
1500
1475
1450
1410
1370
1330
1260
1180
1095
1010
Yellow
5
1235
1215
1190
1160
1120
1075
1020
950
880
805
Red
5
1035
1005
955
915
875
825
770
715
650
575
1002122
BOTTOM or
TWO-SIDES
3,4
Black
2690
2595
2490
2390
2280
2170
2050
1930
1810
1675
Yellow
2180
2145
2095
2045
1980
1905
1820
1725
1615
1490
Orange
1790
1795
1785
1765
1735
1690
1630
1555
1460
1350
Blue
1640
1640
1635
1620
1595
1565
1510
1450
1365
1270
Red
1365
1360
1360
1345
1330
1300
1265
1215
1155
1080
1202422
BOTTOM or
TWO-SIDES
3,4
Black
2645
2545
2445
2340
2230
2110
1990
1810
1685
1580
Blue
2430
2355
2275
2185
2090
1980
1850
1700
1600
1500
Yellow
1850
1825
1795
1760
1705
1625
1540
1465
1380
1280
Orange
1610
1595
1575
1550
1500
1455
1405
1345
1270
1185
Red
5
1445
1430
1405
1380
1350
1315
1265
1215
1150
1075
NOTE
:
1. A filter is required for each return
−
air inlet. Airflow performance includes a 3/4 in. (19 mm) washable filter media such as contained in factory
−
authorized accessory
filter rack. See accessory list. To determine airflow performance without this filter, assume an additional 0.1 in. w.c. available external static pressure.
2. Blower speed taps are not always in the same order. Factory Default blower connections are as follows:
Heating airflow
−
BLUE (also used for Continuous Fan)
Cooling airflow
−
BLACK (enabled when the Y terminal is energized)
ADJUST THE BLOWER SPEED TAPS AS NECESSARY FOR THE PROPER AIR TEMPERATURE RISE FOR EACH INSTALLATION.
3. Airflows over 1800 CFM require bottom return, two
−
side return, or bottom and side return. A minimum filter size of 20” x 25” (508 x 635 mm) is required.
4. For upflow applications, air entering from one side into both the side of the furnace and a return air base counts as a side and bottom return.
5. Highlighted areas indicate that this airflow range is beyond the range allowed for heating. THESE AIRFLOW RANGES MAY ONLY BE USED FOR COOLING.
6. All airflows that are shown in
BOLD
exceed 0.58 Watts per CFM at the given external static pressure.