background image

SERVICE AND TECHNICAL SUPPORT MANUAL

Gas Furnace: (F/G)9MVE

Specifications  subject to change without notice.

440 04 4800 00

30

Sequence of Operation

NOTE

:  Furnace control must be grounded for proper operation

or else control will lock out. Control is grounded through

green/yellow wire routed to gas valve and burner box screw.
Using the schematic diagram in 

Figure 16

, follow the sequence

of operation through the different modes. Read and follow the

wiring diagram very carefully.

NOTE

:  If a power interruption occurs during a call for heat

(W/W1 or W/W1

and

W2), the control will start a 90

second

blower

only ON period two seconds after power is restored, if

the thermostat is still calling for gas heating. The amber LED
light will flash code 1+2 during the 90

second period, after

which the LED will flash a heartbeat (bright

dim), as long as no

faults are detected. After the 90

second period, the furnace will

respond to the thermostat normally.
The blower door must be installed for power to be conducted

through the blower door interlock switch ILK to the furnace

control CPU, transformer TRAN, inducer motor IDM, blower

motor BLWM, hot

surface igniter HSI, and gas valve GV.

1. Two

Stage Heating (Adaptive Mode) with

Single

Stage Thermostat

NOTE

:  The low

heat only switch SW1

2 selects either the

low

heat only operation mode when ON, (see item 2. below) or

the adaptive heating mode when OFF in response to a call for

heat. (See 

Figure 5

) When the W2 thermostat terminal is

energized it will always cause high

heat operation when the

R

to

W circuit is closed, regardless of the setting of the

low

heat only switch. This furnace can operate as a two

stage

furnace with a single

stage thermostat because the furnace

control CPU includes a programmed adaptive sequence of

controlled operation, which selects low

heat or high

heat

operation. This selection is based upon the stored history of the
length of previous gas

heating periods of the single

stage

thermostat.
The furnace will start up in either low

 or high

heat. If the

furnace starts up in low

heat, the control CPU determines the

low

heat on

time (from 0 to 16 minutes) which is permitted

before switching to high

heat.

If the power is interrupted, the stored history is erased and the

control CPU will select low

heat for up to 16 minutes and then

switch to high

heat, as long as the thermostat continues to call

for heat. Subsequent selection is based on stored history of the

thermostat cycle times.
The wall thermostat “calls for heat”, closing the R

to

W circuit.

The furnace control performs a self

check, verifies the

low

heat and high

heat pressure switch contacts LPS and

HPS are open, and starts the inducer motor IDM in

high

speed.

a.

Inducer Prepurge Period

(1.)  If the furnace control CPU selects low

heat

operation the inducer motor IDM comes up to

speed, the low

heat pressure switch LPS closes,

and the furnace control CPU begins a

15

second prepurge period. If the low

heat

pressure switch LPS fails to remain closed the

inducer motor IDM will remain running at

high

speed. After the low

heat pressure switch

re

closes the furnace control CPU will begin a

15

second prepurge period, and continue to run

the inducer motor IDM at high

speed.

(2.) If the furnace control CPU selects high

heat

operation, the inducer motor IDM remains

running at high

speed, and the high

heat

pressure switch relay HPSR is de

energized to

close the NC contact. When sufficient pressure is

available the high

heat pressure switch HPS

closes, and the high

heat gas valve solenoid

GV

HI is energized. The furnace control CPU

begins a 15

second prepurge period after the

low

heat pressure switch LPS closes. If the

high

heat pressure switch HPS fails to close and

the low

heat pressure switch LPS closes, the

furnace will operate at low

heat gas flow rate

until the high

heat pressure switch closes for a

maximum of 2 minutes after ignition.

b.

Igniter Warm

Up

 

At the end of the prepurge period,

the Hot

Surface Igniter HSI is energized for a

17

second igniter warm

up period.

c.

Trial

For

Ignition Sequence

 

When the igniter

warm

up period is completed the main gas valve

relay contact GVR closes to energize the gas valve

solenoid GV

M. The gas valve solenoid GV

M

permits gas flow to the burners where it is ignited by

the HSI. Five seconds after the GVR closes, a

2

second flame proving period begins. The HSI

igniter will remain energized until the flame is sensed

or until the 2

second flame proving period begins. If

the furnace control CPU selects high

heat operation,

the high

heat gas valve solenoid GV

HI is also

energized.

d.

Flame

Proving

 

 When the burner flame is proved

at the flame

proving sensor electrode FSE, the

inducer motor IDM switches to low

speed unless the

furnace is operating in high

heat, and the furnace

control CPU begins the blower

ON delay period and

continues to hold the gas valve GV

M open. If the

burner flame is not proved within two seconds, the

control CPU will close the gas valve GV

M, and the

control CPU will repeat the ignition sequence for up

to three more Trials

For

Ignition before going to

Ignition

Lockout. Lockout will be reset automatically

after three hours, or by momentarily interrupting 115

vac power to the furnace, or by interrupting 24 vac

power at SEC1 or SEC2 to the furnace control CPU

(not at W/W1, G, R, etc.). If flame is proved when

flame should not be present, the furnace control CPU

will lock out of Gas

Heating mode and operate the

inducer motor IDM on high speed until flame is no

longer proved.

e.

Blower

On delay

 

 If the burner flame is proven the

blower

ON delays for low

heat and high

heat are as

follows: 

Low

heat 

 45 seconds after the gas valve GV

M is

opened the blower motor BLWM is turned ON at

low

heat airflow. 

High

heat 

 25 seconds after the gas valve GV

M is

opened the BLWM is turned ON at high

heat airflow.

Simultaneously, the humidifier terminal HUM and

electronic air cleaner terminal EAC

1 are energized

and remain energized throughout the heating cycle.

f.

Switching from Low

 to High

Heat

 

 If the furnace

control CPU switches from low

heat to high

heat, the

furnace control CPU will switch the inducer motor

IDM speed from low to high. The high

heat pressure

switch relay HPSR is de

energized to close the NC

contact. When sufficient pressure is available the

high

heat pressure switch HPS closes, and the

high

heat gas valve solenoid GV

HI is energized.

The blower motor BLWM will transition to high

heat

airflow five seconds after the furnace control CPU

switches from low

heat to high

heat.

g.

Switching from High

 to Low

Heat

 

The furnace

control CPU will not switch from high

heat to

low

heat while the thermostat R

to

W circuit is

closed when using a single

stage thermostat.

h.

Blower

Off Delay

 

When the thermostat is satisfied,

the R to W circuit is opened, de

energizing the gas

Summary of Contents for F9MVE0401410A

Page 1: ...pictures or product labels The signal word WARNING is used throughout this manual in the following manner Safety alert symbol When you see this symbol on the unit and in instructions or manuals be al...

Page 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Page 3: ...Manual Gas Shut off Upstream of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Shade in Final Furnace Settings Below OAT PL9 PL4 PL7 SW 1 SW2 SW3 SW4 O N 8 7 6 5...

Page 4: ...r high stage cooling airflow when a two stage outdoor unit is used Refer to the Adjustments section for set up switch configurations To set the desired cooling airflow 1 Remove blower door 2 Locate A...

Page 5: ...xchanger failures WARNING FURNACE DAMAGE HAZARD Failure to follow this caution may result in reduced furnace life DO NOT redrill orifices Improper drilling burrs out of round holes etc can cause exces...

Page 6: ...ce No 44 Furnace is shipped with No 44 orifices In this example all main burner orifices are the correct size and do not need to be changed to obtain proper input rate Manifold pressure 3 4 in w c 847...

Page 7: ...ssure tap plug to gas valve e Remove jumpers R to W W1 and R to W2 FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Re install manifold pressure...

Page 8: ...TERMINAL 115 VAC 1 0 AMP MAX PL1 LOW VOLTAGE MAIN HARNESS CONNECTOR TERMINALS HARNESS CONNECTOR TRANSFORMER 24 VAC CONNECTIONS 3 AMP FUSE STATUS AND COMM LED LIGHTS SW1 SETUP SWITCHES AND AND ECM BLO...

Page 9: ...0 300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48...

Page 10: ...43 3 8 1 6 42 3 2 1 4 850 44 3 8 1 6 43 3 5 1 5 43 3 6 1 5 43 3 7 1 6 875 44 3 6 1 5 44 3 7 1 6 43 3 4 1 4 43 3 5 1 5 4000 900 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 1219 925 44 3 2 1 4 44 3 4 1...

Page 11: ...re and airflow FURNACE DAMAGE HAZARD Failure to follow this caution may result in S Overheating the heat exchangers or condensing flue gases in heat exchanger areas not designed for condensate S Short...

Page 12: ...SWITCH SW1 7 and 8 POSITION 90 OFF OFF 120 ON OFF 150 OFF ON 180 ON ON Adjust Cooling Airflow High Speed and Low Speed Cooling The ECM blower can be adjusted for a range of airflows for low speed or...

Page 13: ...0 seconds to 180 seconds See table in Adjustments section or refer to unit wiring diagram SW4 3 CFM per ton Adjust OFF Allows additional CFM per ton selections when used with SW 1 5 325 CFM per ton no...

Page 14: ...this method to check limit control it can be established that limit is functioning properly and will operate if there is a restricted return air supply or motor failure If limit control does not funct...

Page 15: ...50 1110 1075 1045 1005 Cooling SW2 OFF OFF ON 725 660 600 520 435 See note 4 OFF ON OFF 780 725 660 615 540 See note 4 OFF ON ON 975 925 875 835 785 750 690 655 610 570 ON OFF OFF 1160 1120 1090 1045...

Page 16: ...1015 825 630 485 405 325 See note 4 OFF ON OFF 1080 895 815 740 690 615 555 475 See note 4 OFF ON ON 1155 1080 1020 940 890 825 785 710 660 590 ON OFF OFF 1310 1260 1195 1140 1075 1025 970 925 875 81...

Page 17: ...sposal CAUTION ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death or property damage Before installing modifying or servicing system main...

Page 18: ...e label located on control door or Figure 15 and the troubleshooting guide which can be obtained from your distributor Retrieving Stored Fault Codes The stored status codes will NOT be erased from the...

Page 19: ...ion device access doors removed WARNING CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective...

Page 20: ...Figure 9 for steps 5 through 14 5 Remove screws securing blower assembly to blower shelf and slide blower assembly out of furnace Detach ground wire and disconnect blower motor harness plugs from blow...

Page 21: ...ture rise as shown in Adjustments Section Adjust temperature rise as shown in Adjustments Section Cleaning Burners and Flame Sensor The following items must be performed by a qualified service technic...

Page 22: ...Surface Igniter NOTE Use propane resistant pipe dope to prevent leaks Do not use Teflon tape 13 Install the gas pipe to the gas valve Figure 12 Igniter Position Side View L12F041 2 in 2 5 mm 3 8 in 3...

Page 23: ...xternal shut off or gas meter 3 Remove control door and set aside 4 Turn electric switch on gas valve to OFF 5 Disconnect external drain from condensate drain elbow or drain extension pipe inside the...

Page 24: ...ring diagram and reconnect wires to flame rollout switch gas valve igniter and flame sensor 10 Turn on gas and electrical supplies to furnace 11 Check furnace operation through two complete heat opera...

Page 25: ...ied 3 8 in 9 5 mm ID tube to the open port on the collector box 6 Insert a field supplied funnel into the tube 7 Pour 1 quart of anti freeze solution into the funnel tube Antifreeze should run through...

Page 26: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MVE Specifications subject to change without notice 440 04 4800 00 26 Figure 15 Service Label 338317 2 Rev H...

Page 27: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MVE Specifications subject to change without notice 27 440 04 4800 00 Figure 16 Wiring Diagram 338317 2 Rev H...

Page 28: ...t flashes When done put setup switch SW1 1 in the OFF position Was there a previous status code other than the heartbeat Go to section below for the status code that was flashed Does the control respo...

Page 29: ...gh heat then switch to low heat check manifold pressure If OK check burner carryover and flame sensor location Clean flame sensor with fine steel wool and recheck current Nominal current is 4 0 to 6 0...

Page 30: ...t high speed and the high heat pressure switch relay HPSR is de energized to close the NC contact When sufficient pressure is available the high heat pressure switch HPS closes and the high heat gas v...

Page 31: ...ll continue operating at cooling airflow for an additional 90 seconds Jumper Y Y2 to DHUM to reduce the cooling off delay to 5 seconds See Figure 4 b Two Stage Thermostat and Two Speed Cooling See Fig...

Page 32: ...ed with a heat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles Whenever W W1 is energized along with Y1 or Y Y2 the furna...

Page 33: ...800 00 Figure 20 Variable Speed Furnace with Single Stage Heat Pump Dual Fuel L09F026 NOTE 9 Figure 21 Variable Speed Furnace with Two Stage Heat Pump Dual Fuel L09F028 NOTE 9 Figure 22 Variable Speed...

Page 34: ...stallation Instructions for additional information and setup procedure 4 When using a Humidity Sensing Thermostat set DEHUMIDIFY OPTIONS to H DE ENRGZD FOR DEHUM 5 Optional connection If wire is conne...

Page 35: ...Module when used Inducer motor capacitor when used Collector box Condensate trap Condensate trap elbow Gaskets WARNING FIRE EXPLOSION ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to f...

Page 36: ...Two stage FEATURE B Base AFUE Efficiency E Extra AFUE Efficiency C Communicating D Dual Certified 2 pipe or 1 pipe R 2 pipe only S Single stage T Two stage N Standard L Low Nox FEATURE 040 40 000 BTU...

Reviews: