background image

INSTALLATION INSTRUCTIONS

R

410A Split System Air Conditioner

421 01 5104 02

7

Specifications subject to change without notice.

Start

Up

CAUTION

!

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this caution may result in minor personal

injury, equipment damage or improper operation.
To prevent compressor damage or personal injury,

observe the following:

S

 

Do not overcharge system with refrigerant.

S

 

Do not operate unit in a vacuum or at negative

pressure.

S

 

Do not disable low pressure switch in scroll compressor

applications.

S

 

Dome temperatures may be hot.

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves

when handling refrigerant and observe the following:

S

 

Front seating service valves are equipped with

Schrader valves.

CAUTION

!

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental

damage.
Federal regulations require that you do not vent refrigerant

to the atmosphere. Recover during system repair or final 

unit disposal.

Follow these steps to properly start up the

system:

1. After system is evacuated, fully open liquid and vapor

service valves.

2. Unit is shipped with valve stem(s) front seated (closed)

and caps installed. 

Replace stem caps after system is opened to

refrigerant flow.  Replace caps finger

tight and tighten

with wrench an additional 1/12 turn

3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure

set point is below indoor ambient temperature.

5. Set room thermostat to COOL and fan control to ON or

AUTO mode, as desired. Operate unit for 15 minutes.

Check system refrigerant charge.

Check Charge

Factory charge amount and desired subcooling are shown

on unit rating plate. Charging method is shown on information

plate inside unit. To properly check or adjust charge,

conditions must be favorable for subcooling charging.

Favorable conditions exist when the outdoor temperature is

between 70

_

F and 100

_

F (21.11

_

C and 37.78

_

C), and the

indoor temperature is between 70

_

F and 80

_

F (21.11

_

C and

26.67

_

C). Follow the procedure below:

Unit is factory charged for 15ft  (4.57 m) of lineset. Adjust

charge by adding or removing 0.6 oz/ft of 3/8 liquid line

above or below 15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less),

allow system to operate in cooling mode at least 15 minutes.

When operating with the Observer Wall Control in

communicating mode, make sure that indoor airflow is set to

“efficiency” during charging. If conditions are favorable, check

system charge by subcooling method. If any adjustment is

necessary, adjust charge slowly and allow system to operate

for 15 minutes to stabilize before declaring a properly

charged system.
If the indoor temperature is above 80

_

F (26.67

_

C), and the

outdoor temperature is in the favorable range, adjust system

charge by weight based on line length and allow the indoor

temperature to drop to 80

_

F (26.67

_

C) before attempting to

check system charge by subcooling method as described

above.
If the indoor temperature is below 70

_

F (21.11

_

C), or the

outdoor temperature is not in the favorable range, adjust

charge for line set length above or below 15ft (4.57 m) only.

Charge level should then be appropriate for the system to

achieve rated capacity. The charge level could then be

checked at another time when the both indoor and outdoor

temperatures are in a more favorable range.

NOTE

: If line length is beyond 80 ft (24.38 m) or greater than

20 ft (6.10 m) vertical separation,  See Long Line Applications

Guideline for special charging requirements.

Major Components

Control Board

The AC control board controls the following functions:

S

Compressor contactor operation

S

Outdoor fan motor operation

S

Compressor external protection

S

Pressure switch monitoring

S

Time Delays

Field Connections

When using communicating control, 4 field wires are required

to be connected to the factory wires already wired to the

DX+DX

C R terminal (see Fig. 10).  Unit as provided by

manufacturer is set up for communicating control.
When used with a standard non

communicating thermostat,

it is recommended to use 3 thermostat control wires to be

connected to R, Y and C. When using 3 wires, all diagnostic

and time delay features are enabled (See Fig. 11).

Disconnect factory provided wires from DX+, DX

, C & R

terminals.  Using factory provided wires, connect to R, C, and

Y on the control board for 3 wire thermostat control.  Connect

field 24V wires to factory provided wires now connected to R,

C, and Y and cap both sides or remove unused factory

provided wires.
When only 2 thermostat control wires are available, units will

function, but some control features are lost. (See Fig. 12).

With only 2 wires connected, the circuit board will be

powered down whenever there is no call for cooling, and the

following will result:

S

Compressor time delay is reduced from 5 minutes to 10
seconds

S

When the thermostat is not calling for cooling, the amber
status light will be off, and no diagnostics codes will be
available

S

All system counters will be reset on each new call for
cooling

Summary of Contents for CSA6

Page 1: ...ility or operation Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Labeling and Signal Words CAUTION WARNING TABLE OF CONTENTS Safety C...

Page 2: ...ee Fig 1 6 Avoid direct tubing contact with water pipes duct work floor joists wall studs floors and walls 7 Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing See Fig 1 8 Ensure that tubing insulation is pliable and completely surrounds vapor tube 9 When necessary use hanger straps which are 1 in 25 4 mm wide and conform to...

Page 3: ...operating ambient in cooling mode is 125 F 51 67_C Make Piping Connections WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves CAUTION UNIT DAMAGE HAZARD Failur...

Page 4: ...ng line sets between 80 and 200 ft 24 38 and 60 96 m and or 20 ft 6 09 m vertical differential refer to Long Line Applications Guideline Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR up to 80 ft 24 38 m Connection and Tube Diameter Connection Diameter Rated Tube Diameter 18 24 30 3 8 3 4 3 4 36 42 48 3 8 7 8 7 8 60 3 8 7 8 1 1 8 Uni...

Page 5: ...using the recommended deep vacuum method of 500 microns An alternate triple evacuation method may be used See triple evacuation method in Service Manual IMPORTANT Always break a vacuum with dry nitrogen Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum metho...

Page 6: ...ired Final Wiring Check IMPORTANT Check factory wiring and field wire connections to ensure terminations are secured properly Check wire routing to ensure wires are not in contact with tubing sheet metal etc Compressor Crankcase Heater When equipped with a crankcase heater furnish power to heater a minimum of 24 hr before starting unit To furnish power to heater only set thermostat to OFF and clos...

Page 7: ...ommunicating mode make sure that indoor airflow is set to efficiency during charging If conditions are favorable check system charge by subcooling method If any adjustment is necessary adjust charge slowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system If the indoor temperature is above 80_F 26 67_C and the outdoor temperature is in the favorable...

Page 8: ... will be turned OFF until the next valid communication Amber Status Light An amber colored STATUS light is used to display the operation mode and fault codes as specified in the troubleshooting section See Table 3 for codes and definitions NOTE Only one fault code will be displayed on the outdoor unit control board the most recent with the highest priority Crankcase Heater Operation The crankcase ...

Page 9: ...RUCTIONS R 410A Split System Air Conditioner 421 01 5104 02 9 Specifications subject to change without notice terminals For operation in non communicating mode wire solenoid valve kit NASA401LS across C and Y terminals ...

Page 10: ... outdoor fan is turned off If the call for cooling continues the control will energize the compressor contactor every 15 minutes If the thermal protector closes at the next 15 minute interval check the unit will resume operation If the thermal cutout trips for three consecutive cycles then unit operation is locked out for 4 hours and the appropriate fault code See Table 3 is displayed CONTACTOR SH...

Page 11: ...il Sensor Fault 55 Coil sensor not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check wiring Thermal Cutout 72 Compressor voltage sensed after start up then absent for 10 consecutive seconds while cooling demand exists Possible causes are internal compressor overload trip or ...

Page 12: ...INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioner 12 421 01 5104 02 Specifications subject to change without notice Figure 9 Single Stage Control Board ...

Page 13: ...ite Red R Wall Control Variable Speed Furnace Fan Coil Outdoor Green Yellow White Red LEGEND 24V FACTORY WIRING 24V FIELD WIRING FIELD SPLICE CONNECTION C DX DX R Figure 11 Non Communicating Standard Thermostat 3 Wire 24V Circuit Connections See Thermostat Installation Instructions for Specific Unit combinations LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION ELECTRICAL OPERAT...

Page 14: ...OM HEAT STAGE 1 HEAT STAGE 2 INDOOR FAN LEGEND 24V FACTORY WIRING 24V FIELD WIRING FIELD SPLICE CONNECTION NOTE Wiring must conform to NEC or local codes Figure 13 Non Communicating Indoor with Observer Communicating Wall Control NAXA00101DB Green Yellow White Red OAT Sensor Communicating Outdoor W2 C Y R C R Wall Control OAT DX R C DX Y G O C Y Y2 R W2 G DX R C DX Non Communicating Indoor NOTE Th...

Page 15: ...as with other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a suction line filter drier in liquid line POE oils absorb moisture rapidly Do not expose oil to atmosphere POE oils may cause damage to certain plastics and roofing materials Wrap all filt...

Reviews: