INSTALLATION INSTRUCTIONS
R
−
410A Split System Air Conditioner
421 01 5104 02
5
Specifications subject to change without notice.
Install Liquid Line Filter Drier Indoor
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Installation of filter drier in liquid line is required.
Filter drier must be wrapped in a heat
−
sinking material
such as a wet cloth while brazing.
Refer to Fig. 3 and install filter drier as follows:
1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5 in. (127 mm) liquid tube.
Flow arrow must point towards indoor coil.
4. Connect and braze liquid refrigerant tube to the filter
drier.
Figure 3
Liquid Line Filter Drier
Refrigerant Tubing Connection Outdoor
Connect vapor tube to fitting on outdoor unit vapor service
valves (see Table 2.) Connect and braze the 3/8” coupling
(provided with the filter drier) to the liquid service valve and
connect and braze the liquid tubing to the other end of this
coupling. Use refrigerant grade tubing.
Sweat Connection
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Service valves must be wrapped in a heat
−
sinking
material such as a wet cloth.
Service valves are closed from factory and ready for brazing.
After wrapping service valve with a wet cloth, braze sweat
connections using industry accepted methods and materials.
Consult local code requirements. Refrigerant tubing and
indoor coil are now ready for leak testing. This check should
include all field and factory joints.
Evacuate Refrigerant Tubing and Indoor Coil
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using
the recommended deep vacuum method of 500 microns. An
alternate triple evacuation method may be used. See triple
evacuation method in Service Manual.
IMPORTANT
: Always break a vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable
of pulling a vacuum of 500 microns and a vacuum gage
capable of accurately measuring this vacuum depth. The
deep vacuum method is the most positive way of assuring a
system is free of air and liquid water. (See Fig. 4)
Figure 4
Deep Vacuum Graph
500
MINUTES
0
1
2
3
4
5
6
7
1000
1500
LEAK IN
SYSTEM
VACUUM TIGHT
TOO WET
TIGHT
DRY SYSTEM
2000
MICRONS
2500
3000
3500
4000
4500
5000
A95424
Final Tubing Check
IMPORTANT
: Check to be certain factory tubing on both
indoor and outdoor unit has not shifted during shipment.
Ensure tubes are not rubbing against each other or any
sheet metal. Pay close attention to feeder tubes, making sure
wire ties on feeder tubes are secure and tight.
Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Do not supply power to unit with compressor terminal box
cover removed.
Be sure field wiring complies with local and national fire,
safety, and electrical codes, and voltage to system is within
limits shown on unit rating plate. Contact local power
company for correction of improper voltage. See unit rating
plate for recommended circuit protection device.
NOTE
: Operation of unit on improper line voltage constitutes
abuse and could affect unit reliability. See unit rating plate.
Do not install unit in system where voltage may fluctuate
above or below permissible limits.
NOTE
: Use copper wire only between disconnect switch and
unit.
NOTE
: Install branch circuit disconnect of adequate size per
NEC to handle unit starting current. Locate disconnect within
sight from and readily accessible from unit, per Section
440
−
14 of NEC.
Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend
wires from disconnect through power wiring hole provided
and into unit control box.