background image

INSTALLATION INSTRUCTIONS

R

410A Split System Air Conditioner

10

421 01 5104 02

Specifications subject to change without notice.

TROUBLESHOOTING

SYSTEMS COMMUNICATION FAILURE

If communication between outdoor unit, control board, and

indoor wall control has failed,  the control will flash the

appropriate fault code. (See table 3)  Check the wiring to the

wall control, indoor and outdoor units.

PRESSURE SWITCH PROTECTION

The outdoor unit is equipped with high

 and low

pressure

switches.  If the control senses the opening of a high or

low

pressure switch, it will de

energize the compressor

contactor, keep the outdoor fan operating for 15 minutes and

display the appropriate fault code. (See table 3)
After a 15 minute delay, if there is still a call for cooling, and

the LPS or HPS is reset, the compressor contactor is

energized.  If the LPS or HPS has not closed after a 15

minute delay, the outdoor fan is turned off.  If the open switch

closes anytime after the 15

minute delay, then the unit will

resume operation with a call for cooling.
If the LPS or HPS trips for five consecutive cycles, then unit

operation is locked out for 4 hours and the appropriate fault

code (See table 3) is displayed.
In the event of a high

pressure switch trip or high

pressure

lockout, check the refrigerant charge, outdoor fan operation

and outdoor coil for airflow restrictions.
In the event of a low

pressure switch trip or low

pressure

lockout, check the refrigerant charge and indoor airflow.

CONTROL FAULT

If the outdoor unit control board has failed, the control will

flash the appropriate fault code. (See table 3)  The control

board should be replaced.

24V BROWN OUT PROTECTION

If the control voltage is less than 15.5volts for at least 4

seconds, the compressor contactor and fan relay are

de

energized.  Compressor and fan operation are not

allowed until control voltage is a minimum of 17.5volts.  The

control will flash the appropriate fault code. (See table 3)

Verify the control voltage is in the allowable range of

18

30volts.

COMPRESSOR VOLTAGE SENSING

The input terminals labeled VR and VS on the control board

(see Fig. 9) are used to detect compressor voltage status,

and alert the user of potential problems. The control

continuously monitors the high voltage on the run capacitor

of the compressor motor. Voltage should be present any time

the compressor contactor is energized, and voltage should

not be present when the contactor is de

energized.

COMPRESSOR THERMAL CUTOUT OR LOSS OF

230V POWER

If the control senses the compressor voltage after start

up,

and is then absent for 10 consecutive seconds while cooling

demand exists, it will de

energize the compressor contactor,

keep the outdoor fan operating for 15 minutes (if 230v power

present) and display the appropriate fault code. (See table 3)

Possible causes are compressor internal overload trip or loss

of high voltage (230V) to compressor without loss of control

voltage.
After a 15 minute delay, if there is still a call for cooling, the

compressor contactor is energized.  If the thermal protector

has not re

set, the outdoor fan is turned off.  If the call for

cooling continues, the control will energize the compressor

contactor every 15 minutes.  If the thermal protector closes,

(at the next 15 minute interval check), the unit will resume

operation.
If the thermal cutout trips for three consecutive cycles, then

unit operation is locked out for 4 hours and the appropriate

fault code (See Table 3) is displayed.

CONTACTOR SHORTED DETECTION

If there is compressor voltage sensed when there is no

demand for compressor operation, the contactor may be

stuck closed.  The control will flash the appropriate fault

code.  Check the contactor and control box wiring.

NO 230V AT COMPRESSOR

I f  t h e  c o m p re s s o r  v o l t a g e  i s  n o t  s e n s e d  w h e n  t h e

compressor should be starting, the contactor may be stuck

open or the unit disconnect or circuit breaker may be open.

The control will flash the appropriate fault code.  Check the

contactor, unit disconnect or circuit breaker and control box

wiring.

TEMPERATURE THERMISTORS

Thermistors are electronic devices which sense temperature.

As the temperature increases, the resistance decreases.

Thermistors are used to sense outdoor air (OAT) and coil

temperature (OCT).
If the outdoor air or coil thermistor should fail, the control will

flash the appropriate fault code. (See table 3).

IMPORTANT

: The outdoor air thermistor and coil thermistor

are factory mounted in the correct locations. Do not re

locate

thermistor sensors.

THERMISTOR SENSOR COMPARISON

The control continuously monitors and compares the outdoor

air temperature sensor and outdoor coil temperature sensor

to ensure proper operating conditions. The comparison is, if

the outdoor air sensor indicates 

10

_

F (

12.22

_

C) warmer

than the coil sensor (or) the outdoor air sensor indicates

20

_

F (

6.67

_

C) cooler than the coil sensor, the sensors

are out of range.
If the sensors are out of range, the control will flash the

appropriate fault code. (See Table 3).

FAILED THERMISTOR DEFAULT OPERATION

Factory defaults have been provided in the event of failure of

outdoor air thermistor and/or coil thermistor.
Thermistor Curve:  The resistance vs. temperature chart

shown in Figure 8 enables the technician to check the

outdoor air and outdoor coil thermistors for proper resistance.

Unplug the thermistor assembly from the circuit board and

measure resistance across each thermistor. For example, if

the outdoor temperature is 60

_

F (15.56

_

C), the resistance

reading across the outdoor air thermistor should be around

16,000  Ohms.

STATUS CODES

Table 3 shows the status codes flashed by the amber status

light. Most system problems can be diagnosed by reading

the status code as flashed by the amber status light on the

control board.
The codes are flashed by a series of short and long flashes

of the status light. The short flashes indicate the first digit in

the status code, followed by long flashes indicating the

second digit of the error code.  The short flash is 0.25 second

ON and the long flash is 1.0 second ON.  Time between

flashes is 0.25 second.  Time between short flash and first

long flash is 1.0 second.  Time between code repeating is 2.5

seconds with LED OFF.
Count the number of short and long flashes to determine the

appropriate flash code. Table 3 gives possible causes and

actions related to each error.

Summary of Contents for CSA6

Page 1: ...ility or operation Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Labeling and Signal Words CAUTION WARNING TABLE OF CONTENTS Safety C...

Page 2: ...ee Fig 1 6 Avoid direct tubing contact with water pipes duct work floor joists wall studs floors and walls 7 Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing See Fig 1 8 Ensure that tubing insulation is pliable and completely surrounds vapor tube 9 When necessary use hanger straps which are 1 in 25 4 mm wide and conform to...

Page 3: ...operating ambient in cooling mode is 125 F 51 67_C Make Piping Connections WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves CAUTION UNIT DAMAGE HAZARD Failur...

Page 4: ...ng line sets between 80 and 200 ft 24 38 and 60 96 m and or 20 ft 6 09 m vertical differential refer to Long Line Applications Guideline Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR up to 80 ft 24 38 m Connection and Tube Diameter Connection Diameter Rated Tube Diameter 18 24 30 3 8 3 4 3 4 36 42 48 3 8 7 8 7 8 60 3 8 7 8 1 1 8 Uni...

Page 5: ...using the recommended deep vacuum method of 500 microns An alternate triple evacuation method may be used See triple evacuation method in Service Manual IMPORTANT Always break a vacuum with dry nitrogen Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum metho...

Page 6: ...ired Final Wiring Check IMPORTANT Check factory wiring and field wire connections to ensure terminations are secured properly Check wire routing to ensure wires are not in contact with tubing sheet metal etc Compressor Crankcase Heater When equipped with a crankcase heater furnish power to heater a minimum of 24 hr before starting unit To furnish power to heater only set thermostat to OFF and clos...

Page 7: ...ommunicating mode make sure that indoor airflow is set to efficiency during charging If conditions are favorable check system charge by subcooling method If any adjustment is necessary adjust charge slowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system If the indoor temperature is above 80_F 26 67_C and the outdoor temperature is in the favorable...

Page 8: ... will be turned OFF until the next valid communication Amber Status Light An amber colored STATUS light is used to display the operation mode and fault codes as specified in the troubleshooting section See Table 3 for codes and definitions NOTE Only one fault code will be displayed on the outdoor unit control board the most recent with the highest priority Crankcase Heater Operation The crankcase ...

Page 9: ...RUCTIONS R 410A Split System Air Conditioner 421 01 5104 02 9 Specifications subject to change without notice terminals For operation in non communicating mode wire solenoid valve kit NASA401LS across C and Y terminals ...

Page 10: ... outdoor fan is turned off If the call for cooling continues the control will energize the compressor contactor every 15 minutes If the thermal protector closes at the next 15 minute interval check the unit will resume operation If the thermal cutout trips for three consecutive cycles then unit operation is locked out for 4 hours and the appropriate fault code See Table 3 is displayed CONTACTOR SH...

Page 11: ...il Sensor Fault 55 Coil sensor not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check wiring Thermal Cutout 72 Compressor voltage sensed after start up then absent for 10 consecutive seconds while cooling demand exists Possible causes are internal compressor overload trip or ...

Page 12: ...INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioner 12 421 01 5104 02 Specifications subject to change without notice Figure 9 Single Stage Control Board ...

Page 13: ...ite Red R Wall Control Variable Speed Furnace Fan Coil Outdoor Green Yellow White Red LEGEND 24V FACTORY WIRING 24V FIELD WIRING FIELD SPLICE CONNECTION C DX DX R Figure 11 Non Communicating Standard Thermostat 3 Wire 24V Circuit Connections See Thermostat Installation Instructions for Specific Unit combinations LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION ELECTRICAL OPERAT...

Page 14: ...OM HEAT STAGE 1 HEAT STAGE 2 INDOOR FAN LEGEND 24V FACTORY WIRING 24V FIELD WIRING FIELD SPLICE CONNECTION NOTE Wiring must conform to NEC or local codes Figure 13 Non Communicating Indoor with Observer Communicating Wall Control NAXA00101DB Green Yellow White Red OAT Sensor Communicating Outdoor W2 C Y R C R Wall Control OAT DX R C DX Y G O C Y Y2 R W2 G DX R C DX Non Communicating Indoor NOTE Th...

Page 15: ...as with other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a suction line filter drier in liquid line POE oils absorb moisture rapidly Do not expose oil to atmosphere POE oils may cause damage to certain plastics and roofing materials Wrap all filt...

Reviews: