ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Page 92
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
6.2.34
@AALO(Data)CiT
Description
This command is used to set the low alarm for a specific channel of a specified
module.
Syntax
@AALO(Data)CiT[CHECKSUM](CR)
@
Delimiter character
AA
The address of the module to be set in hexadecimal format (00 to FF)
LO
The command to set the low alarm
(Data)
The low alarm limit, which should be consistent with the engineering
units format. Refer to Section 4 for details.
Ci
The channel to be set, zero based
T
The alarm type:
M: Momentary Alarm
L: Latched Alarm
Response
Valid Command
!AA[CHECKSUM](CR)
Invalid Command
?AA[CHECKSUM](CR)
!
Delimiter character to indicate a valid command
?
Delimiter character to indicate an invalid command
AA
The address of the responding module in hexadecimal format (00 to FF)
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Examples
Command @03LO-03.000C1L
Response !03
Sets the low alarm limit for channel 1 of module 03 to -03.000 and sets the alarm
type to latched, and returns a response indicating that the command was
successful.
Command @03RLC1