PROFI-8455 – Q&A

1. Q: How do I know the status of the PROFI-8455?

A: You can observe the RUN LED in PROFI-8455 panel. If RUN LED
is light, data is exchanging. Otherwise it must be error in the
previous state. You can see Q&A 3 to solve it.

2. Q: Have I must set the PROFI-8455’s address before power

applied?
A: You can change the address after power applied, but you should
let the PROFI-8455 offline at least 5 second. After 5 second offline,
PROFI-8455 will reset by itself, and then apply the new setting of the
rotary switches.

3. Q: If PROFI-8455 couldn’t establish communication with DP-Master,

what can I do?

A: In General, the PROFI-8455’s error is due to the following
reasons.

1. Parameter Fault- PROFI-8455’s ERR LED will have an interval of
0.5 second in each flash. It may reduce from “error module
selection”.

2, Configuration Fault-PROFI-8455’s ERR LED will have an interval
of 1 second in each flash. It may reduce from “error installation
order”.

3, DP-Master OFFLINE-PROFI-8455’s ERR LED will light until
establish data exchange connection. You should switch DP-Master
status from OFFLINE to OPERATE.

4, DP-Master STOP-PROFI-8455’s ERR LED will flash quickly
(time interval may less then 0.5 second). You should switch
DP-Master status from STOP to OPERATE.

4. Q: Which Modules is faster among the same Module Number

(I-87017 and I-8017H)?
A: I-8K series is faster than I-87K series. It is due to the
communication interface, I-8K use Parallel interface, and I-87K use
the serial communication.

Summary of Contents for PROFI-8455

Page 1: ...cture Status Indicator Address PROFIBUS Data Comm I O Expansion Slot Module Installation Console Prog DL Power Input PROFI 8455 Connector and Pin Assignment The PROFIBUS connector is a standard 9 pin...

Page 2: ...te but is still offline stop mode Check the DP Master is ready to communicate with PROFI 8455 ERR Flash 0 5Sec PROFI 8455 Prm is Fault Note 1 Check the setting of PROFI 8455 in the master interface an...

Page 3: ...connection of active terminating resistors is shown in above circuit diagram The PROFI 8455 doesn t have any terminating resistors inside Therefore users must add the terminator in external In genera...

Page 4: ...e 1 User Parameter User parameter also called system parameter is the basic parameters The number of parameter is fixed regardless of the number of modules In PROFI 8455 there are two kinds of paramet...

Page 5: ...f PROFI 8455 The switch labeled LSB is represented the low nibble of the address and the switch labeled MSB is represented the high nibble of the address For advance setting please refer to PROFI 8455...

Page 6: ...is due to the following reasons 1 Parameter Fault PROFI 8455 s ERR LED will have an interval of 0 5 second in each flash It may reduce from error module selection 2 Configuration Fault PROFI 8455 s E...

Page 7: ...he I 87017 series module the remainder analog input module has sampling rate with 10Hz maximum If you want to use the high sampling module I 8017H and I 87017 is the best choice 6 Q how can I use the...

Reviews: