Status Indicator

PROFI-8455 provide three types of status indicators, they are PWR LED
(yellow), ERR LED (red) and RUN LED (green).

Status Indicator

Meaning

Recommend solution

ERR ON &

RUN OFF

PROFI-8455 is offline

with no valid baud rate

(offline mode*)

Check the address setting of

PROFI-8455 and DP-master.

ERR Flash

(0.1 Sec)

PROFI-8455 detects

baud rate, but is still

offline.(stop mode*)

Check the DP-Master is

ready to communicate with

PROFI-8455.

ERR Flash

(0.5Sec)

PROFI-8455 Prm is

Fault.(Note 1)

Check the setting of

PROFI-8455 in the master

interface and make sure of

the consistency.

ERR Flash

(1 Sec)

PROFI-8455’s Cfg is

fault(Note 2)

Same as above

ERR ON & RUN

ON

PROFI-8455 is in clear

mode*.

Sets the DP-Master from

clear mode to operation

mode

ERR OFF & RUN

ON

PROFI-8455 is in

operation mode*.

PWR Flash

(1 Sec)

PROFI-8455 detect

module(s) offline

Find the reason of the fault of

corresponding module.

Summary of Contents for PROFI-8455

Page 1: ...cture Status Indicator Address PROFIBUS Data Comm I O Expansion Slot Module Installation Console Prog DL Power Input PROFI 8455 Connector and Pin Assignment The PROFIBUS connector is a standard 9 pin...

Page 2: ...te but is still offline stop mode Check the DP Master is ready to communicate with PROFI 8455 ERR Flash 0 5Sec PROFI 8455 Prm is Fault Note 1 Check the setting of PROFI 8455 in the master interface an...

Page 3: ...connection of active terminating resistors is shown in above circuit diagram The PROFI 8455 doesn t have any terminating resistors inside Therefore users must add the terminator in external In genera...

Page 4: ...e 1 User Parameter User parameter also called system parameter is the basic parameters The number of parameter is fixed regardless of the number of modules In PROFI 8455 there are two kinds of paramet...

Page 5: ...f PROFI 8455 The switch labeled LSB is represented the low nibble of the address and the switch labeled MSB is represented the high nibble of the address For advance setting please refer to PROFI 8455...

Page 6: ...is due to the following reasons 1 Parameter Fault PROFI 8455 s ERR LED will have an interval of 0 5 second in each flash It may reduce from error module selection 2 Configuration Fault PROFI 8455 s E...

Page 7: ...he I 87017 series module the remainder analog input module has sampling rate with 10Hz maximum If you want to use the high sampling module I 8017H and I 87017 is the best choice 6 Q how can I use the...

Reviews: