PROFI-5053 PROFIBUS DAQ Module - QuickStart (Apr/2017)
ICP DAS USA, Inc.
|
www.icpdas-usa.com
| 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
1
PROFI-5053
PROFIBUS Remote I/O Module
Quick Start Guide
Introduction
This user guide introduces the user how to implement the PROFI-5000
into their applications in a quick and easy way. Therefore, it only provides
the basic instructions. For more detail information about the PROFI -5000
module, please refer to the PROFI-5000 user manual in the ICP DAS
product CD or download it from ICP DAS web site.
PROFI-5000 Connector and Pin Assignment
Pin No.
Signal
Meaning
3
B-Line
Receive/Transmit data – plus
5
GND
Power ground of active terminator
6
VP
Power 5 volt of active terminator
8
A-Line
Receive/Transmit data - minus
The PROFIBUS connector is a standard 9 -pin D-Sub connector, there are
only 4 pins used in PROFI-5000. The pins VP and GND support the 5 volt
power to active terminal resistor, and the A-Line and B-Line is the data bus.
Status Indicator
PROFI-5045/ PROFI-5050/ PROFI-5051/ PROFI-
5052/ PROFI-5053/ PROFI-5055/ PROFI-5060
It provides two types of status indicator, they are PWR
LED (Red) and RUN LED (Green).
Status Indicator
Meaning
Recommend solution
PWR ON
Master not Ready,
1. Check the address setting
&
Address not Match
of module and DP-master.
RUN OFF
or
2. Sets the DP-Master to
Cfg Fault
operation mode.
3. Make sure of the
consistency of Module
Selection.