PM

-

3133-RCT User’s Manual v1.00   

 

  Last Revised: Mar. 2017                       Page: 1   

Copyright © ICP DAS Co., Ltd.    All Rights Reserved.  

www.icpdas.com

      

 E-mail: [email protected]

 

 

Summary of Contents for PM-3133-RCT Series

Page 1: ...PM 3133 RCT User s Manual v1 00 Last Revised Mar 2017 Page 1 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com...

Page 2: ...9 3 2 Safety 9 3 2 1 Dimension and Latch 9 3 2 2 Mounting and Dismounting 11 3 2 3 Positional Accuracy 12 3 2 4 CT s installation steps 12 Chapter 4 Wiring Diagrams 12 4 1 Connection 13 4 2 Wiring 15...

Page 3: ...39 8 2 1 3 Abort SDO Transfer Protocol 42 8 2 2 PDO Introduction 45 8 2 2 1 PDO COB ID Parameters 45 8 2 2 2 Transmission Type 46 8 2 2 3 PDO Communication Rule 47 8 2 3 NMT Introduction 49 8 2 3 1 Mo...

Page 4: ...e and accurate energy consumption readings from the monitored equipments in real time under operation These compact size and cost effective power meters monitoring equipment with Rogowski Coil CT is r...

Page 5: ...e resulting from the use of this product ICP DAS reserves the right to change this manual at any time without notice The information furnished by ICP DAS is believed to be accurate and reliable Howeve...

Page 6: ...ll Rights Reserved www icpdas com E mail service icpdas com 1 4 1 Limitation of Warranty This warranty does not apply to defects resulting from unauthorized modification misuse or use for reason other...

Page 7: ...rrent 10 A Power Parameter Measurement True RMS voltage Vrms True RMS current Irms Active Power kW Active Energy kWh Apparent Power kVA Apparent Energy kVAh Reactive Power kVAR Reactive Energy kVARh P...

Page 8: ...16 26 AWG torque value 3 0 lb in 5 08mm For Measurement Voltage Aux Power and Alarm Output Use Copper Conductors Only wires range 12 24 AWG torque value 7 0 lb in 7 62mm Use Copper Conductors Only wir...

Page 9: ...The instrument is no longer safe when a Shows clear signs of damage b Does not work c Long storage under extreme conditions d Damage during shipment 3 2 Safety Please use the soft dry clothes to clean...

Page 10: ...r use other CT s is highly prohibited Please read this operation manual carefully before using Please re confirm the measure position PM 3133 series can be installed as rail mounting mode or embedded...

Page 11: ...e Disconnection 1 Open the CT clip to detach the CT do not remove the CT terminal lines if possible Note if you need to remove the terminal lines always detach the CT before removing the CT terminal l...

Page 12: ...agram below shows the variation of accuracy throughout the coil The variation is greatest when the current is positioned near the junction of the connecting cable and the coil where there is some disc...

Page 13: ...hite black white black white black wire sequences CT1 K CT1 L CT2 K CT2 L CT3 K CT3 L Then connect the CT s and close the CT clip Make sure the arrow direction sign on CT s follows current flow direct...

Page 14: ...h each other Since each set of smart meter PM 3133 series and its attached split type clip on CT are calibrated set by set The mix use may cause wrong measurements 4 To install CT s correctly please e...

Page 15: ...33 RCT User s Manual v1 00 Last Revised Mar 2017 Page 15 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com 4 2 Wiring 1P2W 1CT PM 3133 1P3W 2CT PM 3133 3P3W 2CT PM...

Page 16: ...ised Mar 2017 Page 16 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com 3P3W 3CT PM 3133 DIP switch Wiring mode SW 9 SW 10 3P3W 3CT OFF ON 3P4W 3CT PM 3133 DIP swit...

Page 17: ...Voltage Range 250 VAC 30 VDC Max Load Current 5 A at 25 C Operate Time 6 ms Release Time 3 ms 5 2 LED Indicator The PM 3133 has 4 LED to indicate the unit power status RS 485 communication and power...

Page 18: ...ess SW 1 SW 2 SW 3 SW 4 SW 5 SW 6 1 OFF OFF OFF OFF OFF OFF 2 ON OFF OFF OFF OFF OFF 3 OFF ON OFF OFF OFF OFF 4 ON ON OFF OFF OFF OFF 5 OFF OFF ON OFF OFF OFF 6 ON OFF ON OFF OFF OFF 7 OFF ON ON OFF O...

Page 19: ...F ON 39 OFF ON ON OFF OFF ON 40 ON ON ON OFF OFF ON 41 OFF OFF OFF ON OFF ON 42 ON OFF OFF ON OFF ON 43 OFF ON OFF ON OFF ON 44 ON ON OFF ON OFF ON 45 OFF OFF ON ON OFF ON 46 ON OFF ON ON OFF ON 47 OF...

Page 20: ...0 bps ON ON Add the Bias Resistor on RS 485 Network for stable signal The RS 485 master is required to provide the bias for PM 3133 series Otherwise the tM SG4 or SG 785 should be added to provide the...

Page 21: ...h Read Coils Read boolean values of read write location 05h Write Single Coil Set one boolean value of read write location 0Fh Write Multiple Coil Set boolean values of read write location 03h Read Ho...

Page 22: ...ositive E is the two s complement exponent with an offset of 127 i e an exponent of zero is represented by 127 an exponent of 1 by 128 etc M is the 23 bit normal mantissa The highest bit is always 1 a...

Page 23: ...r System Parameter Setting Parameter name Modbus Register Len Data Type Range Default value Units Comment Modicom Format Hex PT_Ratio 44100 0x1003 Word UInt 1 65535 100 0 01 CT_Ratio 44101 0x1004 Word...

Page 24: ...rameter name Modbus Register Len Data Type Range Default value Units Comment Modicom Format Hex Wiring Type 30513 0x0200 Word UInt 9 1P2W 10 1P3W 11 3P3W2CT 12 3P3W3CT 13 3P4W 14 3P3W2CT HW 15 3P3W3CT...

Page 25: ...mp kW_b 34375 34376 0x1116 0x1117 DWord Float kW kvar_b 34377 34378 0x1118 0x1119 DWord Float kvar kVA_b 34379 34380 0x111A 0x111B DWord Float kVA PF_b 34381 34382 0x111C 0x111D DWord Float kWh_b 3438...

Page 26: ...2 0 1A kW_a 34613 34614 0x1204 0x1205 DWord Int32 0 1kW kvar_a 34615 34616 0x1206 0x1207 DWord Int32 0 1kvar kVA_a 34617 34618 0x1208 0x1209 DWord Int32 0 1kVA PF_a 34619 0x120A Word Int 0 1000 0 001P...

Page 27: ...4674 0x1240 0x1241 DWord Int32 0 99999999 0 1kvarh 0 9999999 9 kVAh_tot 34675 34676 0x1242 0x1243 DWord Int32 0 99999999 0 1kVAh 0 9999999 9 Freq_a 34677 0x1244 Word Int 45 65 1Hz 45 65 Freq_b 34678 0...

Page 28: ...132C Word Int 0 1000 0 001PF 0 1 000 kWh_c 34910 34911 0x132D 0x132E DWord Int32 0 99999999 0 1kWh 0 9999999 9 kvarh_c 34912 34913 0x132F 0x1330 DWord Int32 0 99999999 0 1kvarh 0 9999999 9 kVAh_c 3491...

Page 29: ...502 For recovering to default settings dip Init Run Switch SW 4 to Init position for 10 seconds after power on the settings will be changed as default values Must dip back to Run position and repower...

Page 30: ...Rights Reserved www icpdas com E mail service icpdas com 7 1 1 Ethernet configurations In the Power Meter Utility please select Modbus TCP in the Communication Interface Click Search to enter the Comm...

Page 31: ...o Ltd All Rights Reserved www icpdas com E mail service icpdas com Select the power meter which you want to modify parameters from the meter list then click Configuration button to setup the meter par...

Page 32: ...ansaction identifier Protocol identifier Data length upper byte Data length lower byte Transaction identifier Assign by Modbus TCP Master Client Protocol identifier 0 Data length upper byte 0 Data len...

Page 33: ...icpdas com E mail service icpdas com 7 3 Connecting the Power and Host PC without PoE Power over Ethernet PoE The PM 3133 xxx MTCP module can be powered by an IEEE802 3af compliant PoE switch Both Eth...

Page 34: ...W 5 SW 6 1 OFF OFF OFF OFF OFF OFF 2 ON OFF OFF OFF OFF OFF 3 OFF ON OFF OFF OFF OFF 4 ON ON OFF OFF OFF OFF 5 OFF OFF ON OFF OFF OFF 6 ON OFF ON OFF OFF OFF 7 OFF ON ON OFF OFF OFF 8 ON ON ON OFF OFF...

Page 35: ...F ON 40 ON ON ON OFF OFF ON 41 OFF OFF OFF ON OFF ON 42 ON OFF OFF ON OFF ON 43 OFF ON OFF ON OFF ON 44 ON ON OFF ON OFF ON 45 OFF OFF ON ON OFF ON 46 ON OFF ON ON OFF ON 47 OFF ON ON ON OFF ON 48 ON...

Page 36: ...PS Select the different wiring mode Please select the Software setting if 1P2W 1CT or 1P3W 2CT is used Wiring SW 9 SW 10 Software setting OFF OFF 3P3W 2CT ON OFF 3P3W 3CT OFF ON 3P4W 3CT ON ON 8 2 CAN...

Page 37: ...ted to transmit up to four bytes of data Therefore if the data length of the object which the SDO client can read is equal to or less than the permitted data amount the SDO communication will be finis...

Page 38: ...byte is the sub index value d data e 0 s 0 d is reserved for further use e 0 s 1 d contains the number of bytes to be uploaded and byte 4 contains the least significant bit and byte 7 contains the mos...

Page 39: ...oaded seg data It is at most 7 bytes of segment data to be uploaded The encoding depends on the type of the data referenced by index and sub index n It indicates the number of bytes in seg data that d...

Page 40: ...d protocol is needed If e 0 the download SDO segment protocol is necessary s size indicator 0 Data set size is not indicated 1 Data set size is indicated m multiplexer It represents the index sub inde...

Page 41: ...eferenced by index and sub index n It indicates the number of bytes in seg data that do not contain segment data Bytes 8 n 7 do not contain segment data n 0 if no segment size is indicated c It indica...

Page 42: ...ies that users want to modify does not exist or is read only even users wouldn t continue the uncompleted SDO protocol under some special situations When these conditions occur both the client and the...

Page 43: ...mpatibility reason 0604 0047h General internal incompatibility in the device 0606 0000h Access failed due to an hardware error 0607 0010h Data type does not match length of service parameter does not...

Page 44: ...PM 3133 RCT User s Manual v1 00 Last Revised Mar 2017 Page 44 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com generation fails because of an file error...

Page 45: ...ing is given in the table follow Bit Number Value Meaning 31 MSB 0 PDO exits PDO is valid 1 PDO does not exist PDO is not valid 30 0 RTR allowed on this PDO 1 No RTR allowed on this PDO 29 0 11 bit ID...

Page 46: ...g table describes the relationship between the value of the transmission type and the PDO character For example if users used transmission type 0 for the first TxPDO the CANopen device will follow the...

Page 47: ...ndex 0x1800 and the corresponding mapping object is stored in an entry with index 0x1A00 The object with index 0x1801 and the object with index 0x1A01 are a group and so on Therefore before users acce...

Page 48: ...Co Ltd All Rights Reserved www icpdas com E mail service icpdas com COB ID the default PDO COB ID or the PDO COB ID defined by users L the data length about how many bytes the PDO message has PDO msg...

Page 49: ...Control Protocol The NMT communication set can be applied for changing the NMT slave status The following figure shows how to change the different NMT statuses for the PM 3133 CPS Start Remote Node Pr...

Page 50: ...l Rights Reserved www icpdas com E mail service icpdas com Enter Pre Operational Protocol cs NMT command specified 128 enter PRE OPERATIONAL Node ID the node ID of the NMT slave device Reset Node Prot...

Page 51: ...its related objects include 0x100C and 0x100D The 0x100C is the guard time and the 0x100D is the life time factor The node life time is the guard time multiplied by the life time factor The Node Guard...

Page 52: ...3200 0x3208 will map to the PDOs as below table The D0 to D7 represent the CANopen message from Data0 to Data7 No PDO COB ID Data Length D0 D3 D4 D7 1 0x180 Node ID 8 kW Kw_a kWh_a 2 0x280 Node ID 8 k...

Page 53: ...e firmware built in PM 311 CPS In the table the number accompanying letter h indicates that this value is in the hex format General Communication Entries Idx Sidx Description Type Attr Default 1000h 0...

Page 54: ...UNSIGNED 32 RW 180h Node ID 2 transmission type UNSIGNED 8 RW FFh 3 inhibit time UNSIGNED 16 RW 0 4 Reversed 5 event timer UNSIGNED 16 RW 0 1801h 0 largest sub index supported for receive PDO paramet...

Page 55: ...ex supported for receive PDO parameter UNSIGNED 8 RO 5 1 COB ID used by PDO Tx UNSIGNED 32 RW 80000000h 2 transmission type UNSIGNED 8 RW FFh 3 inhibit time UNSIGNED 16 RW 0 4 Reversed 5 event timer U...

Page 56: ...O mapping UNSIGNED 8 RO 2 1 read V_a data INTEGER 32 RO 3202 0120h 2 read I_a data INTEGER 32 RO 3203 0120h 1A05h 0 largest sub index supported for transmit PDO mapping UNSIGNED 8 RO 2 1 read V_b data...

Page 57: ...A0Ah 0 largest sub index supported for transmit PDO mapping UNSIGNED 8 RO 2 1 read kvar kvar_c data INTEGER 32 RO 3204 0320h 2 read kVA Kva_c data INTEGER 32 RO 3205 0320h 1A0Bh 0 largest sub index su...

Page 58: ...ta INTEGER 32 RO 3207 0420h 1A10h 0 largest sub index supported for transmit PDO mapping UNSIGNED 8 RO 2 1 read kvarh_a data INTEGER 32 RO 3208 0120h 2 read Freq_a data INTEGER 32 RO 3209 0120h 1A11h...

Page 59: ...Ratio PT Ratio means potential transformer ratio the default value is 100 and the unit is 0 1 RT Ratio means current transformer ratio the default value is 1 and the unit is 1 Idx Sidx Description Ty...

Page 60: ...kVA Kva_b INTEGER32 RO 0 3 kVA Kva_c INTEGER32 RO 0 4 kVA Kva_tot INTEGER32 RO 0 3206h 0 largest sub index supported for PF UNSIGNED 8 RO 4 1 PF_a INTEGER32 RO 0 2 PF_b INTEGER32 RO 0 3 PF_c INTEGER32...

Page 61: ...1 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com 3 Freq _c INTEGER32 RO 0 4 Freq _avg INTEGER32 RO 0 320Ah 0 largest sub index supported for object UNSIGNED 8 RO...

Page 62: ...service icpdas com 3 Software Wiring Only work when SW9 SW10 is all off UNSIGNED 8 RW 3 1 1P2W 2 1P3W 3 3P3W2CT 4 3P3W3CT 5 3P4W3CT 320Bh 0 largest sub index supported for object UNSIGNED 8 RO 3 1 Set...

Page 63: ...w icpdas com E mail service icpdas com 8 3 3 Application Object The users can write the object the value 65766173h to object with index 1010h and subindex 1 to save the application setting or write th...

Page 64: ...ondition The measure data will be not accuracy as before please do not use any more You need the new CT Q3 If multiple set of meters being installed Can I detach the CT s and mix use with each other P...

Page 65: ...connection make sure the D D is right 5 Confirm the RS 485 master have to provide the bias for PM 3133 series Otherwise the tM SG4 or SG 785 should be added to provide the bias All ICP DAS controllers...

Page 66: ...wye connected system line to line voltages will be the voltages between the terminals A B B C A C On a three phase wye connected system line to ground voltages will be the voltages between the termin...

Page 67: ...uired to set different Display Voltage value If the voltage is not displayed as expected value please refer to the table below and check if the setting value is set accurately Line to Ground Voltage L...

Page 68: ...e on the supply voltage available at your facility Example PRI Voltage 720V SEC Voltage 120V Check the connection diagram three phase Y and delta phase sequence to ensure compatibility Adding potentia...

Page 69: ...a tSH 735 This function allows two master devices connected to different serial ports to share slave devices Modbus mode can be used to convert the Modbus RTU ASCII protocols while raw data mode can b...