![ICP DAS USA P8R8-DIO User Manual Download Page 24](http://html1.mh-extra.com/html/icp-das-usa/p8r8-dio/p8r8-dio_user-manual_3546466024.webp)
5.3.2 Jumper Setting
Each digital input channel can be jumper selected, single-pole, RC filter with a
time constant of 1.2 ms. Refer to Figure 2-2 to see the lost of jumper and it’s
corresponding digital input channel number.
1 2 3 1 2 3
(Default Setting)
(Default Setting)
Without Filter
For DC Signal
With AC Filter
For AC Signal
JP 1 ~ JP 8
JP 9 ~ JP 16
Without Filter
For DC Signal
With AC Filter
For AC Signal
3
2
1
3
2
1
Figure 2-2
P8R8-DIO/P16R16-DIO User Manual (Ver.1.7, Oct. 2011, IMH-009-17)