2.41 ~AA4
Description:
This command is used to read whether Digital Output power-on value and the
Digital Output safe value for a specified module is either active or inactive.
Syntax:
~AA4[CHKSUM](CR)
~
Delimiter character
AA
The address of the module to be read in hexadecimal format (00 to
FF)
4
The command to read the Digital Output power-on value and the
Digital Output safe value
Response:
Valid Command:
!AAPPSS[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character to indicate a valid command
?
Delimiter character to indicate an invalid command
AA
The address of the responding module in hexadecimal format (00 to
FF)
PP
A two-digit hexadecimal value representing the status of the Digital
Output power-on value, where bit 0 corresponds to Digital Output
channel 0, and bit 1 corresponds to Digital Output channel 1, etc.
When the bit is 0, it denotes that the Digital Output power-on is
inactive, and 1 denotes that the Digital Output power-on is active.
SS
A two-digit hexadecimal value representing the status of the Digital
Output safe value, where bit 0 corresponds to Digital Output channel
0, and bit 1 corresponds to Digital Output channel 1, etc. When the bit
is 0, it denotes that the Digital Output safe value is inactive, and 1
denotes that the Digital Output safe value is active.
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address
Note:
Neither the Digital Output power-on value nor the Digital Output safe value has
any effect on Digital Output channels that are associated with alarm outputs.
Examples:
Command: ~0150102
Response: !01
Sets the Digital Output power-on value for module 01 to 01 indicating that
the power-on value for Digital Output channel 0 is active and is inactive
for all others channels and sets the Digital Output safe value to 02
indicating that the safe value for Digital Output channel 1 is active and is
inactive for all others channels, and returns a response indicating that the
command was successful.
Summary of Contents for M-7026
Page 8: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 8 1 3 Pin Assignments...
Page 12: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 12 1 5 Block Diagram...
Page 13: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 13 1 6 Application Wiring...
Page 43: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 43 Section 1 8 1 Analog Input Calibration...
Page 47: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 47 Section 5 1 INIT Mode...
Page 90: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 90 Section 5 2 Dual Watchdog Operation...
Page 113: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 113 Section 2 68 AARECi...
Page 127: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 127 Section 2 62 AADODD...
Page 129: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 129 Related Commands Section 2 61 AADI...
Page 141: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 141 Related Commands Section 2 53 AACECi...
Page 180: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 180...
Page 183: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 183...