M-7026
M-7026 User Manual Rev: 1.5 Date: 2016/03/10
52
2.13 $AA4N
Description:
This command is used to store the current Analog Output value as the
power-on value for Analog Output channel N of a specified module.
Syntax:
$AA4N[CHKSUM](CR)
$
Delimiter character
AA
The address of the module to be set in hexadecimal format (00 to FF)
4
The command to store the current Analog Output value as the
power-on value
N
The Analog Output channel to be set, zero based (0-1)
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character to indicate a valid command
?
Delimiter character to indicate an invalid command
AA
The address of the responding module in hexadecimal format (00 to
FF)
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Note:
The #AAN(Data) command must be sent before this command is used.
Examples:
Command: #012+00.000
Response: >
Sets the output value for Analog Output channel 2 of module 01 to
+00.000 (+0.0 V) and returns a response indicating that the command
was successful.
Command: $0142
Response: !01
Stores the current Analog Output value as the power-on value for Analog
Output channel 2 of module 01 and returns a response indicating that the
command was successful. The power-on value for Analog Output
channel 2 is set to 0.0 V immediately.
Command: $014F
Response: ?01
Attempts to store the power-on value for Analog Output channel 15 of
module 01 and returns a response indicating that the command was
unsuccessful because Analog Output channel 15 does not exist.
Related Commands:
Section 2.5 #AAN(Data), Section 2.19 $AA7N
Summary of Contents for M-7026
Page 8: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 8 1 3 Pin Assignments...
Page 12: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 12 1 5 Block Diagram...
Page 13: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 13 1 6 Application Wiring...
Page 43: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 43 Section 1 8 1 Analog Input Calibration...
Page 47: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 47 Section 5 1 INIT Mode...
Page 90: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 90 Section 5 2 Dual Watchdog Operation...
Page 113: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 113 Section 2 68 AARECi...
Page 127: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 127 Section 2 62 AADODD...
Page 129: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 129 Related Commands Section 2 61 AADI...
Page 141: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 141 Related Commands Section 2 53 AACECi...
Page 180: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 180...
Page 183: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 183...