M-7026
M-7026 User Manual Rev: 1.5 Date: 2016/03/10
36
2.5 #AAN(Data)
Description:
This command is used to set the output value for Analog Output channel N of a
specified module.
Syntax:
#AAN(Data)[CHKSUM](CR)
#
Delimiter character
AA
The address of the module to be set in hexadecimal format (00 to FF)
N
The Analog Output channel to be set, zero based (0-1)
(Data)
The Analog Output value, see Section 1.9.5 for details of the data
format.
Response:
Valid Command:
>[CHKSUM](CR)
Invalid Command:
?
[CHKSUM](CR)
Ignored Command: !
[CHKSUM](CR)
>
Delimiter character to indicate a valid command
?
Delimiter character to indicate an invalid command because the
Analog Output value (Data) is out of range. The Analog Output value
will be restored to the closest value defined in the range settings for
the module.
!
Delimiter character to indicate that the
module’s Host Watchdog flag
is set. The command will be ignored and the Analog Output will be set
to the configured Safe value.
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Examples:
Command: $019000
Response: !01
Sets the output range for Analog Output channel 0 of module 01 to 0 to
20mA and sets the slew rate to change immediately and returns a
response indicating that the command was successful.
Command: #010+05.000
Response: >
Sets the output value for Analog Output channel 0 of module 01 to
+05.000 (5 mA) and returns a response indicating that the command was
successful.
Command: #010+25.000
Response: ?
Attempts to set the output value for Analog Output channel 0 of module
01 to +25.000 (25.0 mA), but returns a response indicating that the
command was unsuccessful because the output value of +25.000(+25
mA) is not within the valid range. The output value will be restored to
closest value defined in the range settings for the module.
Summary of Contents for M-7026
Page 8: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 8 1 3 Pin Assignments...
Page 12: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 12 1 5 Block Diagram...
Page 13: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 13 1 6 Application Wiring...
Page 43: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 43 Section 1 8 1 Analog Input Calibration...
Page 47: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 47 Section 5 1 INIT Mode...
Page 90: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 90 Section 5 2 Dual Watchdog Operation...
Page 113: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 113 Section 2 68 AARECi...
Page 127: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 127 Section 2 62 AADODD...
Page 129: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 129 Related Commands Section 2 61 AADI...
Page 141: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 141 Related Commands Section 2 53 AACECi...
Page 180: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 180...
Page 183: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 183...