M-7026
M-7026 User Manual Rev: 1.5 Date: 2016/03/10
30
2.1 %AANNTTCCFF
Description:
This command is used to set the configuration for a specific module.
Syntax:
%AANNTTCCFF[CHKSUM](CR)
%
Delimiter character
AA
The address of the module to be configured in hexadecimal format
(00 to FF)
NN
The new address of the module in hexadecimal format (00 to FF)
TT
Not used by the M-7026 and should be set to 00.
CC
The new Baud Rate code, see Section 1.9.1 for details. To change
the Baud Rate, the module should first be switched to INIT* mode.
FF
The command used to set the data format, checksum, and filter
settings. See Section 1.9.3 for details of the data format. To change
the checksum settings,
the module should first be switched to INIT*
mode.
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character to indicate a valid command
?
Delimiter character to indicate an invalid command
(Note that if the Baud Rate or checksum settings are changed without
first switching to INIT* mode, the module will return a response
indicating that the command was invalid.)
AA
The address of the responding module in hexadecimal format (00 to
FF)
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Note:
Changes to the address, Type Code, Data Format and Filter settings take
effect immediately after a valid command is received. Changes to the Baud
Rate and checksum settings take effect at the next power-on reset.
Examples:
Command: %0102000600
Response: !02
Changes the address of module 01 to 02 and returns a response
indicating that the command was successful.
Command: %0202000602
Response: !02
Sets the data format for
module 02 to type 2 (2’s complement
hexadecimal). The module returns a response indicating that the
command was successful.
Summary of Contents for M-7026
Page 8: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 8 1 3 Pin Assignments...
Page 12: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 12 1 5 Block Diagram...
Page 13: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 13 1 6 Application Wiring...
Page 43: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 43 Section 1 8 1 Analog Input Calibration...
Page 47: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 47 Section 5 1 INIT Mode...
Page 90: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 90 Section 5 2 Dual Watchdog Operation...
Page 113: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 113 Section 2 68 AARECi...
Page 127: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 127 Section 2 62 AADODD...
Page 129: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 129 Related Commands Section 2 61 AADI...
Page 141: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 141 Related Commands Section 2 53 AACECi...
Page 180: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 180...
Page 183: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 183...