3-8
Getting Started:
PAC-5007(P)/5107(P)/5207/5307 Ver. 1.0, 07/2010 ICP DAS
3.5 Set NET-ID for Controller System
Each μPAC-5x07(P) has a NET-ID Number. The valid Number is from 1 to 255. The default
No. is 1. Net-ID must be unique in the same RS-485 network. To set the NET-ID No.,
please follow below steps.
Related Files & Hardware Connection:
(We use
μPAC-5307
as an example)
1.
Create a file folder named "μPAC-5307" in your hard drive. (Ex. "c:\ μPAC-5307")
2.
Copy the following listed files under “μPAC-5307” folder:
CD:
\Napdos\ISaGRAF\μPAC-5000\Driver\5307\1.00\
3.
Run "7188xw.exe" in your “μPAC-5307” folder.
4.
Link COM1 or COM2 of your PC to COM1 of the PAC through a RS-232 cable.
If your computer has no COM1/COM2 or you use other COM (like COM5) to link the
μPAC-5307, you can change the “C number” in the first line of “7188xw.ini” file.
EX: Using computer’s COM5 to link to μPAC-5307. You need to change C1 to C5.
5.
Switch the “Init*” to “ON” then power it up.
6.
If the connection is OK, “uPAC-5001>” messages will appear on the screen.
Set NET- ID:
7.
Type
"isa5307 *s= 2"
, to set NET-ID to 2.
8.
Switch the “Init*” to “OFF” then power it up.
C1
B115200 P0 D8 S1
F
Xautoexec.bat Xisa5307.exe
w25
C5
B115200 P0 D8 S1
F
Xautoexec.bat Xisa5307.exe
w25
Please type the instruction according to
the controller model. (Ex. isa
5307
*s=2)
PC/HMI
RxD
TxD
GND
PWR1
P.GND
CA0910
OFF
ON