I-8017/I-9017 Series I/O Module User Manual
V3.0.3
P.10
1.1.
Specifications
1.1.1.
I-8017HW/I-8017HCW/I-8017DW
Model
I-8017HW
I-8017HCW
I-8017DW
Analog Input
Channels
8-ch Differential/16-Single-ended
Voltage Input Range
±
1.25, ±2.5, ±5 V, ±10 V
Current Input Range
±
20 mA
(Requires External
125 Ω Resistor)
±
20 mA
(Jumper Select)
Resolution
14-bit
Sample Rate
Single Channel Polling Mode :90K S/s
Single Channel Interrupt Mode: 50K S/s
8 channel Scan Mode : 16 K S/s
Accuracy
0.1% of FSR
Zero Drift
±
0.1 uV/°C
Span Drift
±
10 ppm/°C
Input Impedance
20 K, 200 K, 20 M (Jumper Select)
Input Bandwidth
100 KHz
LED Indicators
System LED Indicator
1 LED as Power Indicator
I/O LED Indicator
16 LEDs as User defined Indicators
EMS Protection
ESD Protection
±4 kV Contact for each Terminal
Summary of Contents for I-8017 Series
Page 14: ...I 8017 I 9017 Series I O Module User Manual V3 0 3 P 14 1 2 Pin Assignments 1 2 1 I 8017HW ...
Page 15: ...I 8017 I 9017 Series I O Module User Manual V3 0 3 P 15 1 2 2 I 8017HCW ...
Page 16: ...I 8017 I 9017 Series I O Module User Manual V3 0 3 P 16 1 2 3 I 8017DW ...
Page 17: ...I 8017 I 9017 Series I O Module User Manual V3 0 3 P 17 1 2 4 I 9017 ...
Page 18: ...I 8017 I 9017 Series I O Module User Manual V3 0 3 P 18 1 2 5 I 9017 15 ...
Page 19: ...I 8017 I 9017 Series I O Module User Manual V3 0 3 P 19 1 2 6 I 9017C 15 ...
Page 26: ...I 8017 I 9017 Series I O Module User Manual V3 0 3 P 26 1 5 3 I 9017C 15 ...
Page 55: ...I 8017 I 9017 Series I O Module User Manual V3 0 3 P 55 ...
Page 83: ...I 8017 I 9017 Series I O Module User Manual V3 0 3 P 83 Click Restore Defaults button ...