background image

                             ICP DAS CO., LTD                           Website: http://www.icpdas.com                               Vol.                                                            

1/2

                        

2019.12

 

Thermocouple Type

Type Code

Thermocouple Type

Temperature Range

0E

-210 to +760°C 

0F

-270 to +1372°C 

10

-270 to +400°C 

11

-270 to +1000°C 

12

0 to +1768°C 

13

0 to +1768°C 

14

0 to +1820°C 

15

-270 to +1300°C 

16

0 to +2320°C 

17

-200 to +800°C 

18

-200 to +100°C 

19

L2

DIN43710

-200 to +900°C 

 

Features

 

I-7018

 

±120 V

DC

 Overvoltage Protection

 

8-channel Diff erential or 6-channel Diff erential and 
2-channel Single-ended Analog Input

 

I-7018R and M-7018R

 

Overvoltage Protection can be up to 240 V

rms

 

8-channel Diff erential Analog Input

 

Current, Voltage or Thermocouple Input

 

3000 V

DC

 Intra-module Isolation

 

Dual Watchdog

 

Wide Operating Temperature Range: -25 to +75°C

 

 I-7018(R)

M-7018(R)

The  I-7018/M-7018  is  an  8-channel  Analog  Input  module  that  provides  
current  and  voltage  input,  as  well  as  thermocouple  input.  The  I-7018R/
M-7018R  is  an  upgraded  version  of  the  I-7018/M-7018  that  includes  an 
extremely  high-quality  protection  mechanism  where  the  overvoltage 
protection  can  be  as  high  as  240  Vrms.  The  I-7018R/M-7018R  is  more 
suitable  for  critically  harsh  environments,  and  the  newly-added  open 
thermocouple detection feature makes the I-7018R/M-7018R more attractive 
than  ever.  The  I-7018/M-7018/I-7018R/M-7018R  also  features  4  kV  ESD 
protection and 3000 V

DC

 intra-module isolation. The specifications for the 

M-7018 and M-7018R are the same as the I-7018 and I-7018R, but provide 
additional  support  for  the  Modbus  RTU  protocol  as  well  as  the  DCON 
protocol.

Model

I-7018

I-7018R

M-7018

M-7018R

Communication

Interface

RS-485

Bias Resistor 

No (Usually supplied by the RS-485 Master. Alternatively, 
add a tM-SG4 or SG-785.)

Format

(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)

Baud Rate

1200 to 115200 bps

Protocol

DCON

Modbus RTU, DCON

Dual Watchdog

Yes, Module (1.6 Seconds), Communication (Programmable)

LED Indicators/Display

System LED Indicator

Yes, 1 as Power/Communication Indicator

I/O LED Indicators

-

7-segment LED Display

-

Isolation

Intra-module Isolation, 
Field-to-Logic

3000 V

DC

EMS Protection

ESD (IEC 61000-4-2)

±4 kV Contact for each Terminal

EFT (IEC 61000-4-4)

±4 kV to Power

Surge (IEC 61000-4-5)

±0.5 kV for Power Line

Power 

Reverse Polarity Protection Yes

Input Range

+10 ~ +30 V

DC

Consumption

1.0 W

Mechanical

Dimensions (L x W x H) 

123 mm x 72 mm x 35 mm 

Installation

DIN-Rail or Wall Mounting

Environment

Operating Temperature

-25 to +75°C

Storage Temperature

-40 to +85°C

Humidity

10 to 95% RH, Non-condensing 

Model

I-7018

I-7018R M-7018

M-7018R

Analog Input

Channels

6 Diff erential 
and  2 
Single-ended, 
or 8 Diff erential


Diff erential

6 Diff erential 
and  2 
Single-ended, 
or 8 Diff erential


Diff erential

Wiring

Diff erential

Sensor 
Types

Thermocouple J, K, T, E, R, S, B, N, C

Voltage

±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V

Current

±20 mA, 0 ~ +20 mA, +4 ~ +20 mA

(requires an optional external 125 Ω resistor)

Resolution

16-bit 

Accuracy

0.1% of FSR

Sampling Rate

10 Hz (Total)

Input Impedance

> 400 kΩ

Common Voltage Protection 25 V

DC

200 V

DC

25 V

DC

200 V

DC

Individual Channel 
Confi guration

-

Yes *Note2 -

Yes *Note3

Overvoltage Protection

±120 V

DC

240 V

rms

±120 V

DC

240 V

rms

Open Wire Detection
(for thermocouple only)

-

Yes

-

Yes

Temperature Outputs 
Consistency

-

Stable Temperature Output 
in the Field

-

8-channel Analog Input Module

 

Introduction

 

Applications

 

System Specifi cations

 

I/O Specifi cations

• Building Automation
• Factory Automation

• Machine Automation
• Remote Maintenance

• Remote Diagnosis
• Testing Equipment

Note 1:  

For highly-accurate thermocouple measurement, ICP DAS recommends selecting
the I-7018Z/I-7019Z module,which features automatic cold-junction compensation
for each channel, ensuring consistent and stable temperature output.

Note 2:

 Firmware version B4.2 or later.

Note 3:

 Firmware version B4.5 or later.