ET-2200 Series Ethernet I/O Modules
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved.
-85 -
Push Mode
4. In the “I/O Pair-connection Settings”, select
“PUSH”
from the “
Mode
” drop-down options.
5. Enter the
IP address for ET-2260 #2 module
in the “
Remote IP
” field.
6. Enter the
TCP Port forET-2260#2 module
in the “
Remote Port
” field.
7. Enter a
DI Count Value for ET-2260 #1 module
in the “
DI Count
” field (Local DI to Remote DO).
The following is an example of a
Push mode
configuration:
Enter
“2”
in the
“DI Count”
field. This means
DI x2 of ET-2260 #1module
is mapped to
DO x2 of
ET-2260 #2module
.
8. Select
Modbus protocol (e.g., “TCP”)
from the
“TCP/UDP”
drop-down options.
9. Click the “
Submit
” button to complete the configuration.
Figure 5-1.6