![ICP DAS USA CAN-2024C User Manual Download Page 14](http://html2.mh-extra.com/html/icp-das-usa/can-2024c/can-2024c_user-manual_3533697014.webp)
CAN-2024C user’s manual (Revision 1.10, Mar/02/2016) ------
14
3.2
Store and Restore Object
Users can write the value 0x65766173 to the object index 0x1010 with
subindex 1 to save application setting, or write the value 0x64616F6C to object
index 0x1011 with subindex 1 to load the factory default. The following table
lists the relative objects which will be stored or restored after writing these two
objects. The factory default for these objects is also shown.
Index
Sub
Index
Description
Factory
Default
2100 h
1
Set Module to Operation Mode when powering on
0
6443 h
1
Error Mode AO channel 0
0
2
Error Mode AO channel 1
0
3
Error Mode AO channel 2
0
4
Error Mode AO channel 3
0
6444 h
1
AO error value of channel 0
0
2
AO error value of channel 1
0
3
AO error value of channel 2
0
4
AO error value of channel 3
0
2004 h
1
Type Code of AO Channel 0
0x33
2
Type Code of AO Channel 1
0x33
3
Type Code of AO Channel 2
0x33
4
Type Code of AO Channel 3
0x33