FAQ-043 

 

Q: How to enable web server for the PDS/7188EN series module? 

 

A: The PDS/7188EN series module contains a built-in web server that allows the settings for the module to 

be remotely modified via a web interface. When the web server has been disabled (Web Server = 0), refer 

to the following two methods to enable the web server. 

 

Method 1: 

Enable web server on PDS by using

 

“console port and command”

.

 

Follow the procedure 

described below:

 

 

1.

 

Power off the PDS module. 

2.

 

Connect the download-cable (CA0910), between the PDS and COM4 of the development PC. 

3.

 

Wire the CA-0910 to PDS, as follows: 

Connect the CA-0910.TX with PDS.TxD 

Connect the CA-0910.RX with PDS.RxD

 

Connect the CA-0910.GND with PDS.GND

 

 

 

 

 

 

 

4.

 

Set the 

“Init/Normal Switch”

 on the PDS module to the in 

“Init”

 position. 

(Or connect the 

INIT* pin to the GND pin

.) 

5.

 

Power on the PDS module. 

 