The sensors work in all voltage and current ranges displayed in the table bellow:

Operating Voltage

Max. Switching Power Max. Switching Current

Peak Current

110Vac

20VA

0.2A

0.5A @20ms

220Vac

20VA

0.1A

0.5A @20ms

5Vdc

2.5W

0.5A

1A @20ms

12Vdc

5W

0.5A

1A @20ms

24Vdc

10W

0.5A

1A @20ms

24Vac:

 NOT recommended

AC Current: 

Use

 

K8 Filter

*

 

in parallel with the coil (A1 A2) of a contactor or relay.

 

DC Current: 

Use 

KD Filter

*

 in parallel with the coil (A1 A2) of a contactor or relay.

 *

On 

accessories.icos.us

 check models and prices of Filters and Mini Contactor

K8 Snubber Filter

 for 

electrical installation (AC) 

(included)

 

Term of Warranty

 

Operation

Typical Connection to Contactor

Electrical Contact of Sensors

 - 

Attention to Install

! Never connect the sensor 
directly to a motor, pump, 
lamp or any other load 
over 20W.
Always use a contactor or 
relay.

Manual

C.01/Oct2017

0.1µF 400V

*

For sale on

 

accessories.icos.us

Flow Switches 

Models for G 1/4” Port

IMPORTANT !

YOU MUST CHECK BEFORE INSTALLATION

For installations according to this guide: 

02 (two) years warranty. 

Incorrect installation cancels the warranty.

 

All Sensors have been tested and approved during the manufacture process.

Reed Switch 20W/VA: Protect the Electrical Contact of your Sensor

Siemens 3RT1015 Contactor

Initial: 31.7VA

Rated: 5.1VA

icos.net

• Liquids with solid particles and/or fouling

 require prior 

testing. Use filter before the Sensor to prevent the internal piston 

from locking. Not recommended for industrial water waste.

• Liquids with ferrous and/or magnetic particles

 require 

technical analysis: the Sensor contains magnetic components 

inside. Use a magnetic filter before the Sensor to avoid 

deposition/settling that will prejudice its operation.

Direct connection 

to the 

sensor

Use 

22R 5W

*

resistor

 in series

Use

24Vdc Voltage

• 

AUXILIARY CONTACTOR (mini contactor) mind the distance:

• 

SOLENOID VALVE or POWER CONTACTOR: 

 

Use 

mini contactor

 

or 

auxiliary relay

.

• 

ELECTRONIC EQUIPMENT: 

 

› 

Interface relay/relay coupler:

 Use 

4K7 10W resistor

 

› 

Timing relay and frequency inverter:

 Use 

220R 5W

*

 resistor

.

Follow the instructions below to protect and extend the shelf life of the sensor:

Questions? Call us BEFORE you install:

+55 (15) 

3032.9190

levelsensor.icos.us 

datasheets.icos.us

 

videos.icos.us

K8

 for AC

KD

 for DC

Snubber 

Filter

Installing the snubber 

filter extends the 

lifespan of the sensor’s 

electrical contact.

 

On

 

datasheets.icos.us

 

available technical specifications

+55 (15) 

3032.9190

Reed Switches are hermetically sealed 

contacts actuated by a magnetic field.

The life expectancy of a reed switch refers to a kind of load to be 

used. Reed Switches of the highest reliability are applied in our 

sensors, and their life expectancy can reach above two million 

operations. However, when they are switching lamps, inductive or 

capacitive loads, this number may decrease.

Switching Power

It is important to consider that the power specified by an electrical 

load is often referred to the permanent working state. 

 

For higher power, use an auxiliary relay or contactor as recommended 

below, or similar.

Note:

 Reed Switches have reached over one million operations in 

tests with contactor and

 

K8

snubber filter

.

PROTECTION PROCEDURES BELOW DESCRIBED CAN 

IMPROVE THE REED SWITCH PERFORMANCE

Flow Switches and Level Switches for liquids

K8

Filter mounted in parallel 

with the coil of an AC contactor, 

increases the contact life.

KD

Filter mounted in parallel 

with the coil of a DC relay, 

increases the contact life.

Important

: For distances 

greater than 40m

, use 24Vdc voltage.

•Timing relay

•Frequency inverter

•Etc.

Important

: For installation with 

relay coupler

, use 4K7 10W resistor.

• Switching inductive loads

? Risk of failure (welding of the Reed Switch Contact) 

due to CAPACITANCE, which 

can occur depending on the distance and cable used in the connection to the contactor.

• Connecting the sensor to a contactor in long distances, use resistor:

This resistor dampens the peak voltage caused by the 

capacitance of cables and electronic equipment input. 

• Connecting the sensor to an electronic equipment: