Icon Process Controls ProCon C300 Series Operating Manual Download Page 27

C300 Series Operating Manual

27

◀◀

|

Troubleshooting

1. 

LCD display is not bright

 

Possible Causes:

 Instrument or LCD Screen power supply failure.

 

Solutions:

 Check whether the power supply is connected or not, and check whether the power supply wire of the sensor is connected in 

the wrong direction.

2. 

No current output

 

Possible Causes:

 It could be a fault in the current module or a wiring fault.

 

Solutions:

 Please check that the current output wiring is correct. Please refer to the wiring terminal diagram in the instructions.

3. 

The output current of the transmitter does not match the display current.

 

Possible Causes:

 Current output may not be correctly calibrated.

 

Solutions:

 Please re-calibrate the 20mA output.

4. 

There is a

 

 

on the screen.

 

Possible causes:

 The transmitter does not communicate properly with the sensor.

Solutions:

 Check whether the signal line of the sensor is 

correct. Please refer to the wiring diagram in the instruction.

5. 

Measurements display results fluctuate greatly.

 

Possible causes:

 Sensor wiring error or low display rate setting.

 

Solutions:

 Check wiring or increase display rate appropriately.

6. 

7. 

8. 

Warranty

Icon Process Controls

 warrants this product to be free from significant deviations in material and workmanship for a period of one year 

from the date of purchase. If repair is necessary and has not been the result of abuse or misuse within the warranty period, please return 

to 

Icon Process Controls

 and amendment will be made without any charge. 

We Instruments

 Customer Service Center will determine if 

product problem is due to deviations or customer abuse. Out of warranty products will be repaired on a charge basis.
Authorization must be obtained from 

Icon Process Controls

 Customer Service Center to issue a RIR number before returning items for 

any reason. When applying for authorization, please include date requiring the reason of return. Instruments must be carefully packed to 

prevent damage in shipment and insured against possible damage or loss. 

Icon Process Controls

 will not be responsible for any damage 

resulting from careless or insufficient packing.

Warning:

 Damage as a result of inadequate packaging is the User / distributor’s 

 

responsibility. Please follow the guidelines below before transporting.
Use the original packaging material if possible, when transporting back the unit for repair. Otherwise wrap it with bubble pack and use a 

corrugated box for better protection. Include a brief description of any faults suspected for the convenience of Customer Service Center, if 

possible. If there are any questions, feel free to contact our Customer Service Center or distributors.

by

Summary of Contents for ProCon C300 Series

Page 1: ...C300 Series Controller Conductivity TDS Resistivity Salinity Operating Manual...

Page 2: ...Structure 9 Measurement Settings Quick Start 12 Calibration Settings Quick Start 13 Alarm Settings Quick Start 14 Current Settings Quick Start 15 Communication Settings Quick Start 16 System Settings...

Page 3: ...s specified measurements 3 The analyzer has been stored for a long time in an environment where the temperature exceeds 70 C The analyzer must be installed by licensed professionals in accordance with...

Page 4: ...54 F 0 3 C Temp Compensation 32 302 F 10 150 C Temp Compensation Manual or Automatic Stability pH 0 01pH 24h ORP 1mV 24h Output Two 4 20mA 20 4mA 0 20mA Communication RS485 MODBUS RTU Relay Control Co...

Page 5: ...ay common Temp Temperature Sensor NC 1 High set relay resting position Temp Temperature Sensor NO 2 Low set relay working position Input Measurement COM 2 Alarm relay common Ref Reference NC 2 Low set...

Page 6: ...C300 Series Operating Manual 6 Instrument Installation...

Page 7: ...ort Press press the button and release immediately if not specified below means short press Long Press press the button for 3 seconds and then release it Press and hold hold the button for a while and...

Page 8: ...300 Series Operating Manual 8 Display Descriptions Check all pipe connections and electrical connections before use The instrument will display as shown in the figure below after the power is turned o...

Page 9: ...urement Electrode pH ORP Temperature Type NTC2 252 k NTC10 k Pt100 Pt1000 Default Offset 0 00 Default Input Automatic Default Manual N A Unit C Default F Calibration S S C Standard solution calibratio...

Page 10: ...arm High Alarm Limit Hysteresis 100 Default Current setting Current 1 Channel Major measured value Default Temperature Output Type 4 20mA 20 4mA 0 20mA Upper Limit 14 00 Default for pH 2000 Default fo...

Page 11: ...w Standard Medium High Backlight 30 sec 1 min 5 min Default 15 min 30 min Always on Password No password Default Series No XXXXXXXXXX Version VER6 1 00 Restore Calibration Parameter Maintenance Curren...

Page 12: ...C300 Series Operating Manual 12 Measurement Settings Quick Start...

Page 13: ...C300 Series Operating Manual 13 Calibration Settings Quick Start...

Page 14: ...C300 Series Operating Manual 14 Alarm Settings Quick Start...

Page 15: ...C300 Series Operating Manual 15 Current Settings Quick Start...

Page 16: ...C300 Series Operating Manual 16 Communication Settings Quick Start...

Page 17: ...C300 Series Operating Manual 17 System Settings Quick Start...

Page 18: ...C300 Series Operating Manual 18 Maintenance Settings Quick Start...

Page 19: ...standard instruments with the temperature measured by the D300 If there is an error you can use the temperature offset to modify it assuming that the temperature measured by D300 is 25 C and the tempe...

Page 20: ...8 85 4 20 7 02 9 73 Calibration Setup Press ESC and ENT Calibration Setup If you are prompted to enter the password you need to enter the password set in advance If the password is not set you can dir...

Page 21: ...e 2 Save the results and it can be queried next time The pH value of the buffer is measured at 25 C please select the correct buffer please refer to P30 Buffer Table Before calibration the electrode c...

Page 22: ...and it can be queried next time The pH value of the buffer is measured at 25 C please select the correct buffer please refer to P30 Buffer Table Before calibration the electrode can be activated by so...

Page 23: ...S C Choose ORP single point calibration and put the sensor into standard liquid follow the instruction to operate Save the results and it can be queried next time 2 5 ORP onsite calibration Choose ons...

Page 24: ...ticking sound after the PH value exceeds 10 00 At this time in the measurement mode High Alarm will be displayed in the lower left corner At this time the normally open end of the relay is closed and...

Page 25: ...password just select Save There is no password by default when the product leaves the factory In the restore factory settings there is calibration recovery and parameter recovery Calibration restore...

Page 26: ...1 output current one positive and Com output current negative if the multimeter displays a mA value of 3 98mA press direction key to modify until the current value displayed on the multimeter is the...

Page 27: ...aterial and workmanship for a period of one year from the date of purchase If repair is necessary and has not been the result of abuse or misuse within the warranty period please return to Icon Proces...

Page 28: ...28 22 0005 01 20 23 Need a great sensor Pair your D300 Series controller with the industry s most innovative and reliable sensing technology iconprocon com...

Reviews: