34
BACnet / Boilers
Boiler Device Object Types/Property Support
Table 31. BACnet Boiler Object Types/Property Support Table
Property
Device
Binary
Input
Binary
Output
Binary
Value
Analog
Input
Analog
Output
Analog
Value
Multi
Input
Multi
Output
Multi
Value
Object Identifier
R
R
R
R
R
R
R
R
R
R
Object Name
R
R
R
R
R
R
R
R
R
R
Object Type
R
R
R
R
R
R
R
R
R
R
System Status
R
Vendor Name
R
Vendor Identifier
R
Model Name
R
Firmware Revision
R
App S/W Revision
R
Protocol Revision
R
Services Supported
R
Object Types Supported
R
Object List
R
Max APDU Length
R
Segmentation Support
R
APDU Timeout
R
Number APDU Retries
R
Max master
R
Max Info Frames
R
Device Address Binding
R
Database Revision
R
Present Value
R
W
W
R
W
W
R
W
W
Status Flags
R
R
R
R
R
R
R
R
R
Event State
R
R
R
R
R
R
R
R
R
Out-of Service
R
R
R
R
R
R
R
R
R
Units
R
R
R
R
R
R
Priority Array
R
R
R
R
R
Relinquish Default
R
R
R
R
R
Polarity
R
R
Inactive Text
R
R
Active Text
R
R
R - readable using BACnet services
W - readable and writable using BACnet services
OBJECT LISTINGS
Boiler Device Object Initial Values
Note:
Point listings have been changed completely from earlier versions of this listing.
Table 32. BACnet/Boiler Device Object
Property Name
ID
BACnet Data Type
RW
Initial Value
(Mirius)
Initial Value
(ETH-1000)
Object_Identifier
75
Object Identifier
RW
Device, 520081
Device, 520081
Object_Name
77
Character String
RW
Water Heater-01
Water Heater-01
Object_Type
79
Enumerated
R
Device
Device