32
BACnet / Boilers
BACNET / BOILERS
Figure 36. XP XWH Circulating Water Heaters (Virtual Bacnet Device Via ICC Gateway)
PRODUCT DESCRIPTION
The Mirius is a multiprotocol RS-485 to RS-485 gateway. The ETH-1000 is an Ethernet to RS-485 multiprotocol gateway. These
products supports native BACnet, connecting directly to IP or the MS/TP LAN using baud rates of 4800, 9600, 19200, 38400, 57600,
76800, and 115200. As shipped the devices are configured as a BACnet Server.
All XI
TM
MXi
TM
controls provide communications via propriety protocol with the ICC Gateway. The Mirius supports BACnet MS/TP
communications and the ETH- 1000 supports BACnet/IP to access data available at the display plus control of a limited number of
points such as Operating Setpoint.
PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS)
BACnet Standardized Device Profile (Annex L):
BACnet Application Specific Controller (B-ASC)
BACnet Boiler Interoperability
Table 26. BACnet Boiler Interoperability Building Blocks Supported (Annex K):
Data Sharing - ReadProperty-A (DS-RP-A)
Data Sharing - ReadProperty-B (DS-RP-B)
Data Sharing - ReadPropertyMultiple-B (DS-RPM-B)
Data Sharing - WriteProperty-A (DS-WP-A)
Data Sharing - WriteProperty-B (DS-WP-B)
Data Sharing - WritePropertyMultiple-B (DS-WPM-B)
Data Sharing – COV-B (DS-COV-B) (BACnet/IP only)
Device Management-Dynamic Device Binding-A (DM-DDB-A)
Device Management-Dynamic Device Binding-B (DM-DDB-B)
Device Management-Dynamic Object Binding-B (DM-DOB-B)
Device Management-Device Communication Control-B (DM-DCC-B)
Device Management – ReinitializeDevice-B (DM-RD-B)
Segmentation Capability:
Segmentation not supported