Chapter 2. Preparing for installation
This section provides information about the rack, required tools, and an installation
overview.
Rack requirements
The Type 7198 and 7199 appliances can use a standard 19 in (48.26 cm) rack with a
minimum of 28 in. (71.1 cm) of depth. When planning the installation, keep in
mind:
v
The rack must provide rear mounting columns. The appliance requires both
front and rear mounting support.
v
There must be at least 30 in. (76.20 cm) of free space behind the rack frame to
remove replaceable parts.
v
The ambient temperature in the operating environment and within the rack
should not exceed 95° F (35° C).