Table 39. Specifications for power cords used with the TS4500 tape library xx5 frame models (continued)
Length and type of power cord
Part number
and feature
code
1
Type of service receptacle
Dual 4.3 m (14 ft.) 250 V ac, 15A, single phase
power cord, watertight 15A plugs. This power
cord is for US and Canada.
23R9972 / 9985
Russellstoll 3743U2 or 9R23U2W receptacles, or
Russellstoll 3913U2 or 9C23U2 connectors
Uses receptacle #9
Dual 4.3 m (14 ft.) non-watertight, 250 V ac, 10
A power cord with IEC 60320 C14 connector.
This power cord can be used worldwide to
connect to spare outlets on FC 1950 PDUs. It
can be used in an adjacent library frame or to a
customer-provided PDU that is mounted
external to the library frames.
46X7337 / 9989
IEC 60320 C13
Uses receptacle #13
Dual 4.3 m (14 ft.) power cords with NEMA
L6–30P non-watertight 30A plug, 200–240 V ac,
30 Amps. This power cord is for US, Canada,
Latin America, and Japan.
39M5416 / 9954
(Used with FC
1951 only)
NEMA L6–30R
Uses receptacle #10
Dual 4.3 m (14 ft.) power cords with watertight
Russellstoll 3750DP 30A plug, 200–240 V ac, 30
Amps. This power cord is used in US, Chicago,
Canada, Latin America, and Japan.
39M5418 / 9955
(Used with FC
1951 only)
Russellstoll 3753 or 9R33UOW receptacle, or a
Russellstoll 3933 or 9C33UO connector
Uses receptacle #11
Dual 4.3 m (14 ft.) power cords with IEC-309
p+n+g 32A plug, 200–240 V ac single phase, 32
Amps. This power cord is used in Europe, the
Middle East, and Africa.
39M5414 / 9956
(Used with FC
1951 only)
IEC-309 p+n+g
Uses receptacle #2
Dual 4.3 m (14 ft.) power cords with PDL
56P332 32A plug, 200–240 V ac single phase, 32
Amps. This power cord is used in Australia and
New Zealand.
39M5419 / 9957
(Used with FC
1951 only)
1–gang, 3–pin 32A socket, PDL 56SO332 or
equivalent
Uses receptacle #12
Dual 4.3 m (14 ft.) non-watertight power cords
with 30A plug type Shin Ju SJ-3302, 200–240 V
ac, 30 Amps. This power cord is used in North
and South Korea.
39M5420 / 9958
(Used with FC
1951 only)
200–250 V ac single phase
Uses receptacle #3
Dual 4.3 m (14 ft.) power cords, unterminated
(without a power plug), 200–240 V ac single
phase, 30 Amps maximum, with IRAM and
BSMI agency certifications. Wire size 4 mm
2
.
This is the recommended cord for Argentina,
Taiwan, Europe, the Middle East, and Africa if
an unterminated power cord is preferred.
23R7324 / 9959
(Used with FC
1951 only)
Not specified (no plug supplied)
Dual 4.3 m (14 ft.) power cords, unterminated
(without a power plug), 200–240 V ac single
phase, 30 Amps maximum, with CCC
certification. This is the recommended power
cord for China.
23R9543 / 9966
(Used with FC
1951 only)
Not specified (no plug supplied)
Note:
Each feature code ships two power cords so that dual power is supported.
Power Receptacles
Chapter 2. Planning
95
Summary of Contents for TS4500
Page 1: ...IBM TS4500 Introduction and Planning Guide EC SC27 5990 06 IBM...
Page 4: ...iv IBM TS4500 Introduction and Planning Guide...
Page 8: ...viii IBM TS4500 Introduction and Planning Guide...
Page 10: ...x IBM TS4500 Introduction and Planning Guide...
Page 12: ...xii IBM TS4500 Introduction and Planning Guide...
Page 49: ...2 and 4 Figure 9 B accessor in Service Bay B Chapter 1 Overview 31...
Page 88: ...70 IBM TS4500 Introduction and Planning Guide...
Page 99: ...Figure 17 Access panel for Fibre Channel and Ethernet cable routing Chapter 2 Planning 81...
Page 186: ...Korea Notice Russia Notice 168 IBM TS4500 Introduction and Planning Guide...
Page 217: ......
Page 218: ...IBM Printed in USA...