Table
13.
DS4800
Storage
Subsystem
operational
vibration
specifications
Parameter
Value
Frequency
sweep
5
Hz
-
150
Hz
-
5
Hz
Wave
form
Sinusoidal,
0.25
g
Acoustic
noise
lists
the
maximum
sound
levels
emitted
by
the
storage
subsystem.
Table
14.
DS4800
Storage
Subsystem
sound
levels
Measurement
Level
Sound
power
(normal
operation)
6.0
bels
Sound
pressure
(normal
operation)
60
dBA
These
levels
are
measured
in
controlled
acoustical
environments
according
to
ISO
7779
and
are
reported
in
accordance
with
ISO
9296.
The
declared
sound
power
levels
indicate
an
upper
limit,
below
which
a
large
portion
of
machines
operate.
Sound
pressure
levels
in
your
location
might
exceed
the
average
1-meter
values
stated
because
of
room
reflections
and
other
nearby
noise.
Electrical
requirements
This
section
provides
information
regarding
site
power
and
wiring,
storage
subsystem
AC
power
requirements,
and
power
cord
routing
instructions.
Consider
the
following
information
when
preparing
the
DS4800
Storage
Subsystem
installation
site:
v
Protective
ground
–
Site
wiring
must
include
a
protective
ground
connection
to
the
AC
power
source.
Note:
Protective
ground
is
also
known
as
safety
ground
or
chassis
ground.
v
Circuit
overloading
–
Power
circuits
and
associated
circuit
breakers
must
provide
sufficient
power
and
overload
protection.
To
prevent
possible
damage
to
the
unit,
isolate
its
power
source
from
large
switching
loads
(such
as
air
conditioning
motors,
elevator
motors,
and
factory
loads).
v
Power
failures
–
If
a
total
power
failure
occurs,
the
unit
automatically
performs
a
power-up
recovery
sequence
without
operator
intervention
after
power
is
restored.
Table
15.
IBM
System
Storage
DS4800
AC
power
requirements
Low
Range
High
Range
Nominal
Voltage
110
220
Voltage
90
to
132
VAC
198
to
264
VAC
Frequency
(Hertz)
50
to
60
Hz
50
to
60
Hz
Minimum
Operating
Current
3.0
A
a
1.5
A
b
Maximum
Operating
Current
3.0
A
a
1.5
A
b
Maximum
Surge
Current
4.0
A
a
2.0
A
b
Chapter
1.
Introduction
25
||
||
||
||
|
|
Summary of Contents for TotalStorage DS4800
Page 2: ......
Page 18: ...xvi IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 168: ...140 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 216: ...188 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 220: ...192 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 240: ...212 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 246: ...218 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 249: ......
Page 250: ...Part Number 22R6614 Printed in USA GC26 7845 01 1P P N 22R6614...