Minimum
service
clearances
Several
factors
influence
final
cabinet
placement.
In
addition
to
adequate
cable
length
and
staying
within
safe
floor
loading
limits
for
your
installation
site,
observe
the
minimum
clearances
required
for
service
of
the
racks
in
the
Cluster
1350.
You
might
want
to
plan
for
extra
space
around
the
racks
to
allow
movement
of
racks
for
service.
shows
the
clearances
needed
for
servicing
a
rack
in
the
Cluster
1350.
Note
that
the
service
clearances
for
the
sides
of
the
rack
are
not
required
for
operation,
but
only
for
servicing
the
PDUs.
Front
Front
Back
Back
112.5 inch (286 cm)
36 inch (91.4 cm)
36 inch (91.4 cm)
required clearance
required clearance
86 inch (218 cm)
86 inch (218 cm)
30”
30 inch (76.2 cm)
required clearance
for service of PDUs
30”
30 inch (76.2 cm)
required clearance
for service of PDUs
required clearance
front to back
required clearance
side to side
required clearance
side to side
required clearance
side to side
When
planning
the
installation
of
a
large
cluster
and
you
want
to
arrange
the
racks
in
several
rows,
you
must
maintain
a
minimum
aisle
width
of
91.4
cm
(36
inches)
as
shown
in
This
will
allow
enough
space
for
the
front
and
back
covers
of
the
racks
to
open.
An
aisle
width
of
122
cm
(48
inches)
might
be
more
appropriate
if
you
want
to
make
sure
that
you
have
enough
room
to
move
the
rack
to
gain
access
to
the
sides
for
servicing
the
PDUs.
Figure
1.
Cabinet
clearances
required
for
service
©
Copyright
IBM
Corp.
2007
13
Summary of Contents for System Cluster 1350
Page 1: ...IBM System Cluster 1350 Installation and Service Guide...
Page 2: ......
Page 3: ...IBM System Cluster 1350 Installation and Service Guide...
Page 28: ...12 IBM System Cluster 1350 Installation and Service Guide...
Page 46: ...30 IBM System Cluster 1350 Installation and Service Guide...
Page 50: ...34 IBM System Cluster 1350 Installation and Service Guide...
Page 58: ...42 IBM System Cluster 1350 Installation and Service Guide...
Page 65: ......
Page 66: ...Part Number 44R5023 Printed in USA 1P P N 44R5023...