SAN Volume Controller 2145-8F4 and SAN Volume Controller
2145-8F2 environment requirements
Before the SAN Volume Controller 2145-8F4 or SAN Volume Controller 2145-8F2 is
installed, the physical environment must meet certain requirements. This includes
verifying that adequate space is available and that requirements for power and
environmental conditions are met.
Input-voltage requirements
Ensure that your environment meets the following voltage requirements.
Voltage
Frequency
200 to 240 V single phase ac
50 or 60 Hz
Power requirements for each node
Ensure that your environment meets the following power requirements.
The power that is required depends on the node type and whether the redundant
ac power feature is used.
Components
Power requirements
SAN Volume Controller 2145-8F4 and 2145
UPS-1U
520 W
SAN Volume Controller 2145-8F2 and 2145
UPS-1U
520 W
For each redundant ac-power switch, add 20 W to the power requirements.
Circuit breaker requirements
The 2145 UPS-1U has an integrated circuit breaker and does not require additional
protection.
Environment requirements without redundant ac power
Ensure that your environment falls within the following ranges if you are not
using redundant ac power.
Environment
Temperature
Altitude
Relative
humidity
Maximum wet
bulb
temperature
Operating in
lower altitudes
10°C to 35°C
(50°F to 95°F)
0 to 914.4 m
(0 to 3000 ft)
8% to 80%
noncondensing
23°C (74°F)
Operating in
higher altitudes
10°C to 32°C
(50°F to 88°F)
914.4 to 2133.6 m
(3000 to 7000 ft)
8% to 80%
noncondensing
23°C (74°F)
Turned off
10°C to 43°C
(50°F to 110°F)
0 to 2133.6 m
(3000 to 7000 ft)
8% to 80%
noncondensing
27°C (81°F)
Storing
1°C to 60°C
(34°F to 140°F)
0 to 2133.6 m
(0 to 7000 ft)
5% to 80%
noncondensing
29°C (84°F)
2
IBM System Storage SAN Volume Controller: Models 2145-8F2 and 2145-8F4 Hardware Installation Guide