Step 3. Checking the Customer Environment
Check the customer environment as follows:
v
Verify with your installation planning representative or the customer that any
station-protector boxes used are correctly installed according to the
Site and
Hardware Planning Information manual.
v
Make sure the customer is aware that the recommended temperature for this system
is 24° C (75° F) and the recommended relative humidity is 45%. The following are
the acceptable operating ranges:
– Temperature: 10° C (50° F) to 38° C (100° F)
– Humidity: 8% to 80%
v
Make sure the customer is aware that the front and rear service clearances around
the CEC drawer and rack should be 36 inches (900 mm). The service clearances are
important for proper air circulation, weight distribution, and safety to both the service
representative and the customer.
Chapter 1. Setting Up the System
3