Table 2. N6200 series clearance dimensions (continued)
Service
Front
76.2 cm (30 in.)
Rear
76.2 cm (30 in.)
Table 3. N6200 series environmental requirements
Operating temperature maximum range
50° F to 104° F (10° C to 40° C)
Operating temperature recommended range
68° F to 77° F (20° C to 25° C)
Nonoperating temperature range
-40° F to 158° F (-40° C to 70° C)
Operating relative humidity
20 to 80% noncondensing
Nonoperating relative humidity
10 to 95% noncondensing (in
original container)
Recommended operating temperature relative humidity
range
40 to 55%
Maximum wet bulb temperature
28° C (82° F)
Maximum altitude
3050 m (10,000 ft.)
Acoustic level
55.5 dBA, 7.5 bels at 23° C
The following tables list the maximum electrical power for the N6200 series
systems and the electrical requirements for different configurations of the N6200
series systems.
Table 4. N6200 series systems maximum electrical power
System
Maximum electrical power
N6200 series systems
100-240 V ac, 12-8 A, 50-60 Hz.
In the following tables,
Worst-case
indicates a system running with one PSU and
high fan speed.
Typical Per PSU/System, two PSUs
indicates a system running one
PSU on one circuit and a system running two PSUs on two circuits.
Note:
Electrical requirements for systems containing performance accelerator, Flash
Cache, and Flash Cache 2 modules are measured with the maximum number of
these modules installed in the system. The maximum power draw is 25W.
Table 5. N6210 electrical requirements–one controller node, with one 256-GB Flash Cache
module
Input voltage
100 to 120V
200 to 240V
Worst-
case,
single
PSU
Typical
Worst-
case,
single
PSU
Typical
Per PSU
System,
two PSUs
Per PSU
System,
two PSUs
Input current
measured, A
4.22
1.52
3.03
2.11
0.83
1.66
6
IBM System Storage: N6200 Series Hardware and Service Guide
Summary of Contents for N6270
Page 12: ...xii IBM System Storage N6200 Series Hardware and Service Guide...
Page 16: ...xvi IBM System Storage N6200 Series Hardware and Service Guide...
Page 18: ...xviii IBM System Storage N6200 Series Hardware and Service Guide...
Page 20: ...xx IBM System Storage N6200 Series Hardware and Service Guide...
Page 46: ...20 IBM System Storage N6200 Series Hardware and Service Guide...
Page 130: ...104 IBM System Storage N6200 Series Hardware and Service Guide...
Page 134: ...108 IBM System Storage N6200 Series Hardware and Service Guide...
Page 146: ...120 IBM System Storage N6200 Series Hardware and Service Guide...
Page 147: ......
Page 148: ...Printed in USA GA32 0838 04...