2 Checking the ground/earth path
Procedure B
This procedure checks for a ground/earth
resistance of one ohm or less at the receptacle
ground/earth pin using the CE meter.
The wall breaker should be OFF.
1. Using the CE meter, measure the
resistance from the ground/earth pin of the
receptacle to building ground/earth. The
reading should be one ohm or less.
2. For metal receptacle shells, also measure
the resistance from the ground/earth pin of
the receptacle to the metal shell. This
reading should be 0.1 ohm or less.
Note:
Digital meters may give unstable resistance
readings if leakage current is flowing in the
building ground/earth circuit. If the reading
appears unstable, or is greater than one
ohm, contact your branch office installation
planning representative or field manager.
Chapter 1. Beginning the Installation
1-5
Summary of Contents for Multiprise 3000 S/390
Page 1: ...S 390 Multiprise 3000 Enterprise Server R IBM Installation Manual SY24 6154 03...
Page 2: ......
Page 3: ...S 390 IBM Installation Manual SY24 6154 03...
Page 8: ...vi Installing the System...
Page 14: ...xii Installing the System...
Page 34: ...1 20 Installing the System...
Page 40: ...2 6 Installing the System...
Page 78: ...5 20 Installing the System...
Page 156: ...6 78 Installing the System...
Page 160: ...7 4 Installing the System...
Page 172: ...B 4 Installing the System...
Page 173: ......
Page 175: ...Spine information IBM S 390 Installation Manual...