Model 1164-95X rear door heat exchanger:
Learn about the specifications of the 1164-95X rear door heat exchanger (feature code EC05).
Model 1164-95X rear door heat exchanger specifications
Table 79. Dimensions for the 1164-95X rear door heat exchanger
Width
1
Depth
Height
Weight (empty)
Weight (filled)
600 mm (23.6 in.)
129 mm (5.0 in.)
1950 mm (76.8 in.)
39 kg (85.0 lb)
48 kg (105.0 lb)
1.
The width is the inside width of the machine when installed in the U space of the rack. The width of the front
bezel is 482 mm (19.0 in.).
Water specifications
v
Pressure
– Normal operation: <137.93 kPa (20 psi)
– Maximum: 689.66 kPa (100 psi)
v
Volume
– Approximately 9 liters (2.4 gallons)
v
Temperature
Figure 31. Attachment brackets
54
Site and hardware planning
Summary of Contents for 8408-44E
Page 1: ...Power Systems Site and hardware planning IBM...
Page 2: ......
Page 3: ...Power Systems Site and hardware planning IBM...
Page 16: ...xiv Site and hardware planning...
Page 18: ...2 Site and hardware planning...
Page 22: ...6 Site and hardware planning...
Page 51: ...Figure 19 Model 0555 and 7014 S25 plan view Site and hardware planning 35...
Page 192: ...176 Site and hardware planning...
Page 204: ...188 Site and hardware planning...
Page 205: ......
Page 206: ...IBM Printed in USA...