Table 116. Electrical
Electrical characteristics
Properties
Power requirements
275 W
Voltage
100 - 240 V ac
Frequency
50 - 60 Hz
Maximum thermal output
938.3 Btu/hr
Phase
1
kVA
0.281
Table 117. Environmental and acoustical requirements
Environment/Acoustical
Operating
Storage
Airflow direction
Rear-to-front
Temperature, ambient operating
0°C - 40°C (32°F - 104°F)
Temperature (fan failure) operating
0°C - 35°C (32°F - 95°F)
Temperature, storage
-40ºC to +85ºC (-40°F to 185°F)
Relative humidity range
(non-condensing)
10% - 90% RH
10% - 95% RH
Maximum altitude
3050 m (10000 ft)
4573 m (15000 ft)
Heat dissipation
1100 Btu/hr
Acoustic noise
Less than 65 dB
G8264R RackSwitch specification sheet
Hardware specifications provide detailed information for your IBM BNT RackSwitch, including
dimensions, electrical, power, temperature, environment, and service clearances.
Table 118. Dimensions
Height
Width
Depth
Weight (maximum)
44 mm (1.73 in.)
439 mm (17.3 in.)
513 mm (20.2 in.)
10.5 kg (23.1 lb)
Table 119. Electrical
Electrical characteristics
Properties
Power requirements
375 W
Voltage
100 - 240 V ac
Frequency
50 - 60 Hz
Maximum thermal output
1280 Btu/hr
Phase
1
kVA
0.383
Table 120. Environmental and acoustical requirements
Environment/Acoustical
Operating
Storage
Airflow direction
Rear-to-front
Temperature, ambient operating
0°C - 40°C (32°F - 104°F)
Temperature (fan failure) operating
0°C - 35°C (32°F - 95°F)
Temperature, storage
-40ºC to +85ºC (-40°F to 185°F)
Site and hardware planning
85
Summary of Contents for 8408-44E
Page 1: ...Power Systems Site and hardware planning IBM...
Page 2: ......
Page 3: ...Power Systems Site and hardware planning IBM...
Page 16: ...xiv Site and hardware planning...
Page 18: ...2 Site and hardware planning...
Page 22: ...6 Site and hardware planning...
Page 51: ...Figure 19 Model 0555 and 7014 S25 plan view Site and hardware planning 35...
Page 192: ...176 Site and hardware planning...
Page 204: ...188 Site and hardware planning...
Page 205: ......
Page 206: ...IBM Printed in USA...