7025 Deskside F50 Series
Dimensions
Height
620 mm 24.3 in.
Width
245 mm 9.6 in.
Width with Pedestal
350 mm 13.7 in.
Depth
695 mm 27.3 in.
Depth with Pedestal
745 mm 29.3 in.
Weight
Minimum configuration
30 kg 65 lbs.
Maximum configuration
55 kg 120 lbs.
Electrical
Power source loading typical in kVA
0.52
Power source loading maximum in kVA
0.56
Voltage range (V ac)
100 to 127 or 200 to 240 (autoranging)
Frequency (hertz)
50 or 60
Thermal output (typical)
975 Btu/hr
Thermal output (maximum)
2050 Btu/hr
Power requirements (typical)
285 watts
Power requirements (maximum)
600 watts
Power factor
0.8 - 0.96
Inrush current
³
50 amps
Maximum altitude
2135 m (7000 ft.)
Temperature Requirements
Operating
16 to 32°C
(60 to 90°F)
Non-Operating
10 to 43°C
(50 to 110°F)
Humidity Requirements
Operating
Non-Operating
(Noncondensing)
8 to 80%
8 to 80%
Wet Bulb
23°C (73°F)
27°C (80°F)
Noise Emissions
¹
Operating
Idle
L
WAd
5.8 bels
5.5 bels
L
pAm
N/A
N/A
<L
pA
>
m
41 dBA
38 dBA
Impulsive or prominent discrete tones
No
No
Clearances
Front
Back
Left
Right
Install/Air Flow
²
76mm(3 in)
152mm(6 in)
51mm(2 in)
51mm(2 in)
Service
Install so that it can be moved to an area providing 457 mm (18 in.) on the
front and 457 mm (18 in) on the left side.
Footprint
2
Width
350mm(13.7 in)
Depth
975mm(38.4 in)
1. See “Noise Emission Notes” on page 336 for definitions of noise emissions positions.
2. The amount of space needed by the unit during normal operation is indicated by the footprint dimensions.
3. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
Chapter 2. Physical Characteristics of Systems
65
Summary of Contents for 7012 397
Page 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 2: ......
Page 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 11: ...Appendix Notices 385 Index 387 Contents ix...
Page 12: ...x Site and Hardware Planning Information...
Page 16: ...xiv Site and Hardware Planning Information...
Page 18: ...xvi Site and Hardware Planning Information...
Page 26: ...8 Site and Hardware Planning Information...
Page 238: ...220 Site and Hardware Planning Information...
Page 246: ...228 Site and Hardware Planning Information...
Page 284: ...266 Site and Hardware Planning Information...
Page 296: ...278 Site and Hardware Planning Information...
Page 366: ...348 Site and Hardware Planning Information...
Page 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Page 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Page 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Page 384: ...366 Site and Hardware Planning Information...
Page 402: ...384 Site and Hardware Planning Information...
Page 404: ...386 Site and Hardware Planning Information...
Page 413: ......
Page 414: ...Printed in USA SA38 0508 20...
Page 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...