to the fourth row. The bottom-right corner of the alarm history screen displays two
numbers: an ordering number of the event in the log, followed by the total number
of events in the log.
If there are no events in the log, the message
No events in log
is displayed on the
alarm history screen.
For more information, see “Retrieving the alarm history” on page 37.
Meters
The meters screens provide the following meters information:
v
Output watts, VA, current, power factor, voltage, and frequency
v
Input voltage and frequency
v
Battery voltage and percentage charged
v
DC bus voltages
Control screens
The following table describes the available control screens.
Table 7. Control screens
Control screen
Description
Go to Bypass
Transfers the UPS system to internal Bypass mode.
When the Go to Bypass command is issued, the screen displays the
Manual
Bypass Comment Sent
message for 5 seconds. The option then changes to Go to
Normal.
When the Go to Normal command is issued, the screen displays the
Normal Mode
Command Sent
message for 5 seconds. The option then changes to Go to Bypass.
Battery test
Schedule Battery Test: yes | Cancel Battery test: no
Starts a manual battery test.
See “Testing a battery” on page 54.
Reset error state
Reset Alarms: yes | no
Manually clears any latched alarms, such as bad battery detected or DC Bus
OV/UV, and then performs a self-diagnostics test of the LCD, alarm sounds, and
fans.
If a bad battery alarm was also active, resets the battery test status to Not
Tested.
Load segments
Load segment 1: on | off
Load segment 2: on | off
These on/off commands override automatic load segment on/off controls that are
made by the Automatic Start Delay and Automatic On Battery Shutdown settings.
See “Configuring load segments” on page 38.
Restore factory settings
Restore Factory Settings: yes | no
Available only in Standby mode.
Restoring the factory settings:
v
Returns all user-configurable EEPROM settings to default factory settings
v
Resets all pending on/off commands
v
Clears the alarm history and resets all statistic values and time stamps
v
Resets the battery test status
v
Initiates the Self Diagnostics test
Chapter 3. Operating the uninterruptible power supply
31
Summary of Contents for 11000 VA LCD 5U
Page 2: ......
Page 13: ...Taiwan Class A compliance statement 71 Index 73 Contents xi...
Page 14: ...xii 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 40: ...26 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 56: ...42 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 60: ...46 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 76: ...62 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 86: ...72 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 90: ...76 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 91: ......
Page 92: ...Part Number 60Y1454 Printed in USA 1P P N 60Y1454...