Remove the right internal battery module. With the required three people, use the plastic tabs to
pull the right internal battery module completely out of the bay. Place the internal battery
module on a sturdy, flat surface.
If you are installing another UPS, repeat step 7a on page 5 to step 7d.
8.
The UPS and extended battery module are very heavy. See the following table to determine the
handling requirements for safely lifting and installing these devices.
Table 1. UPS and extended battery module handling requirements
Machine
type-model or
part number
Product description
Weight
Handling requirement
5395-9KX
11000 VA 5U rack UPS
35 kg (77 lb) (without internal
battery modules)
Three persons
69Y1986
11000 VA 3U extended battery
module
79 kg (174 lb)
Specially trained persons, a
lifting device, or both
9.
Using the handling requirements in Table 1, align the rear hold-down brackets on the sides of the
UPS or extended battery module with the inner rails. Carefully slide the UPS or extended battery
module into the rack cabinet.
Rear
hold-down
bracket
10.
Secure the front of the UPS or extended battery module to the rack cabinet with four M5 x 16 mm
screws.
6