About Status indicators
The SIM’s two status LEDs indicate the operating status as shown in the table below.
LED 1
LED 2
State
Description, LED status indication
Rapid Flash
Rapid Flash
Power up or
Resetting
Startup checks and initialization
Off
Off
Standby
LED 1 Off = No Flame or Sparking
LED 2 = Burner-On Call state
Off
On
Pre-Purge
or Inter-
Purge
LED 1 Off = No Flame or Sparking
LED 2 = Burner-On Call state
On
On
Heating
LED 1 On = Flame detected
LED 2 = Burner-On Call state
Rapid Flash
On
Igniting
LED 1 flashing = Electrode Sparking
LED 2 = Burner-On Call state
Off
Flashing
Lockout
An operating limit was exceeded or a sequence
failed or an external sensor fault was detected.
Flash
Alternately
with LED 2
Flash
Alternately
with LED 1
Fail-Safe
A critical internal fault was detected. Fail Safe
requires a power cycle.
Table 1
LED status indicators
1.4.3.5 Error logs
The controller records all errors present at the time of an error event in a log.
These logs date back to the original power-up, organized by date, time,
classification, and type. For every error record, there is a "Details" button that
provides:
Minor errors
. An abnormal condition exists that does not present an
immediate safety hazard.
Major errors
. A condition exists that may be a safety hazard. The boiler
enters an extended purge then the fan and pump are stopped. The boiler
must be checked and restarted.
Exception
: The Ign. Trials Exceeded
error will time-out for one hour before the system attempts re-ignition.
11
1.4.3 Status
Summary of Contents for V-10
Page 1: ...V 10 TOUCHSCREEN CONTROLLER MANUAL VX SERIES...
Page 40: ...Intentionally left empty...
Page 50: ...Intentionally left empty...
Page 66: ...Intentionally left empty...
Page 97: ...Wiring diagram Opt Out DHW Figure 22 Opt Out DHW wiring diagram 95 Wiring diagram Opt Out DHW...
Page 102: ......