Description
US Installations
1
1
,
2
2
Canadian Installations
2
,
3
3
J
Clearance to non-
mechanical air supply inlet
to building or the
combustion air inlet to any
other appliance
6 in (15 cm) for appliances
≤ 10,000 Btuh (3 kW), 12 in
(30 cm) for appliances >
10,000 Btuh (3 kW) and ≤
100,000 Btuh (30 kW), 36
in (91 cm) for appliances
>100,000 Btuh (30 kW)
6 in (15 cm) for appliances
≤ 10,000 Btuh (3 kW), 9 in
(23 cm) for appliances >
10,000 Btuh (3 kW) and ≤
50,000 Btuh (15 kW), 12 in
(30 cm) for appliances >
50,000 Btuh (15 kW)
K
Clearance to mechanical
air supply inlet
6 ft (1.83 m)
3 ft (91 cm) above if within
10 ft (3 m) horizontally
L
Do not terminate above
paved sidewalk or paved
driveway
7 ft (2.13 m)
4
Vents cannot be located
above public walkways or
other areas where
condensate or vapor can
cause a nuisance or
hazard*
M
Clearance under veranda,
porch, deck or balcony
12 in (30 cm)
5
*
Table 5
Vent/air inlet termination clearances
Warning
Important!:
Maintain at least the minimum separation of exhaust vent termination from
boiler intake air as illustrated in
,
,
and
. Failure
to do so can result in a dangerous situation where exhaust gasses are re-ingested with
combustion air. Damage to the boiler can result from a failure to maintain these
separations. Third party vent termination kits and concentric wall penetration kits that
do not maintain these minimum separations must
not
be used. Improper installation
will void the warranty. Do not use proprietary InnoFlue or PolyPro PPs terminals
without specific approval from IBC.
Sidewall direct vent with separate vent and air pipes must be terminated as follows:
Locate the intake air and exhaust vent terminations on the same plane (side) of the
building.
1
In accordance with the current CAN/CSA-B149 Installation Codes.
2
If locally adopted installation codes specify clearances different than those illustrated, then the most stringent shall apply.
3
In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
4
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both
dwellings.
5
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
31
3.7.6 Sidewall vent termination
Summary of Contents for SL SERIES
Page 8: ...Intentionally left empty...
Page 14: ...Intentionally left empty...
Page 66: ...Figure 49 Electric wiring connections 62 Section Installation...
Page 78: ...Intentionally left empty...
Page 92: ...Intentionally left empty...
Page 106: ...Internal wiring diagram Figure 53 Internal wiring diagram 102 Section Appendices...
Page 107: ...Sequence of Operation Figure 54 Sequence of Operation 103 Sequence of Operation...
Page 109: ...105 Exploded views of boiler parts...
Page 114: ...110 Section Appendices...
Page 122: ...Intentionally left empty...