9. Check the results and confirm the correct settings when you return the boiler to high fire,
and then to low fire.
Note
For natural gas, clock the gas meter to confirm full maximum rating plate input.
10. To exit the
Test Operation
screen, select
Back
.
11. Remove the call for heat.
12. If a manometer is connected to the gas valve inlet gas pressure port:
a. Turn off the gas supply at the external gas shut-off valve.
b. Disconnect the manometer.
c. Tighten the inlet pressure port screw with a Torx 15 screwdriver.
13. Remove the analyzer probe, and install the test port plug.
14. Turn on the gas supply shut off valve, and soap test for leaks.
Fuel
High fire
Low fire
CO max
PPM
Range %
Target %
Range %
Target %
Natural Gas
9.0 - 10.0
9.5
8.2 - 9.2
8.7
<150
Propane
10.3 - 11.3
10.8
9.3 -10.3
9.8
< 250
Table 12
Combustion test target ranges - CO
2
/ Maximum CO
Note
: Low Fire CO
2
should be at least 0.5% lower than High Fire CO
2
71
6.3.3 Adjusting the gas valve
Summary of Contents for SL Series
Page 8: ...Intentionally left empty...
Page 12: ...Figure 5 Top view SL 40 399 G3 Figure 6 Bottom view SL 40 399 G3 8 Section Specifications...
Page 14: ...Intentionally left empty...
Page 64: ...Figure 40 Electric wiring connections 60 Section Installation...
Page 76: ...Intentionally left empty...
Page 96: ...Intentionally left empty...
Page 108: ...Intentionally left empty...
Page 110: ...Internal wiring diagram Figure 46 Internal wiring diagram 106 Section Appendices...
Page 111: ...Sequence of operations Figure 47 Sequence of Operation 107 Sequence of operations...