Annual Maintenance
Check
Check the Error Logs for any issues.
□
Inspect the flue gas exhaust and air intake connections. All connections should be tight and
leak free.
□
Inspect flue gas exhaust piping, combustion air piping and terminations.
□
Inspect the boilers interior and vacuum if required.
□
Check for water, gas and condensate leaks in the boiler and around the boiler.
□
Check the condensate trap and clean if required. Re-fill the trap and re-install the trap hook.
□
Check the water pressure, expansion tank and pumps.
□
Check the electrical connections.
□
Check the ignition electrode and remove oxidation from the electrode. Replace if necessary.
□
Check the gas valve and ignition cable.
□
Check the controller settings.
□
Check the burners flame. Should be a quick and quiet ignition across the full burner.
□
If required, clean the heat exchanger and the burner. Refer to instructions in the boiler's
Installation and Operating Instructions
manual
□
Note
Installers should inquire of local water purveyors as to the suitability of their supply for use in
hydronic heating systems.
If water quality is questionable, a local water treatment expert must be consulted for testing,
assessment and, if required, treatment.
Alternatively, water or hydronic fluid of known quality can be brought to the site.