5.0 Troubleshooting
This section includes a table of warning and error messages that may appear on the appliance as well
faults that may appear on the air handling appliance app.
A problem that does not prevent the operation of the air handler is declared as a "warning". A problem
that prevents the appliance from operating is declared as an "error" and the appliance is shut down.
5.1 Measuring voltage on AHU boards
The control voltage transformer is not bonded to the AHU cabinet. When measuring the voltage supplied
to the individual control circuit, you must reference the common post of the circuit. If you measure to
ground or to another common terminal, misleading readings of approximately 14V will occur.
To test for nominal 24V, reference the adjacent COM connection. For example, to test voltage at
Compressor S1 terminal, measure for VAC between Compressor COM and Compressor S1.
5.2 Pump not energized
If the pump is not energizing:
In the
IBCconnect
app, go to
Advanced Settings
, and check that
Pump Enabled
is set to "on".
In the
IBCconnect
app, go to
Basic Settings
, and check that
Heat Mode
is not set to "Heat
Pump": During Stage 1 heat pump heating, the AHU pump is not energized by design, to avoid
interfering with circulation through the heat pump. AHU pump is energized at Stage 2 call for
heat.
Check the AHU board for blown pump fuse—the only fuse rated for 10A.
5.3 Fault Codes
Fault Code/Error Message
Description
Possible Fix
Inlet Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
Outlet Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
Aux Air In Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
Air Out Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
Cool Air Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
A/C Temperature Sensor
Sensor not connected or
faulty.
Check the sensor. For resistance
reading, see Table 13.
Summary of Contents for AHU Series
Page 1: ...INSTALLATION OPERATING MANUAL Air Handling appliances AHU 800 AHU1200 AHU 1600...
Page 2: ......
Page 5: ...5 3 Fault Codes 67 Air handling appliance parts diagram 70 3...
Page 6: ...This page is intentionally left blank...
Page 18: ...This page is intentionally left blank...
Page 60: ...This page is intentionally left blank...