SL 30-175, SL 45-260 MODULATING GAS BOILERS
5.3 trouBlesHooting guide
SYMPTOM
DIAGNOSIS
REMEDY
AIRFLOW ERROR
LCD Screen Message:
Error – Insufficient Air Flow
Insufficient combustion airflow;
soft error; will retry in 5 minutes
Check fan operation
• Check lead is attached at fan.
• Cycle power off/on; listen for fan initialization.
if no action, focus your attention on the fan
itself.
Check for fouled
reference lines and air
sensor
• Check clear vinyl air pressure line for
presence of water. after disconnecting from
black air pressure sensor, blow clear
(do not
blow into sensor).
Check for exhaust re-
ingestion, or repeated power interruptions .
• Ensure condensate trap is not blocked.
• Go to Advanced Diagnostics and check
differential air pressure sensor (at rest and
with fan on). see
Section 5.2.3
.
Check achieved fan
power
in advanced diagnostics, during Pre-purge, Fan
Pressure (FP) should move close to required
Pressure (rP); if FP only 120-150 vs. rP of
[250 or 300], then check for actual vent system
blockage: (a) disconnect intake within boiler
case; (b) open burner then fan/gas valve looking
for debris.
Water noise in vent.
Excess condensate in
venting.
• Check condensate trap for obstructions.
Remove obstructions and refill condensate
trap with water.
• Check vent length, size and configuration.
WARNING
Never attempt to repair
the control module (circuit
board). If the control module
is defective, replace it
immediately.