Combustion Test Target Ranges

Figure 1 Gas valve and fan

The Low Fire (zero-offset) valve adjustment cap on the gas valve has been factory set. Do not adjust this screw in the field 

unless indicated  in these instructions. 

After converting the unit to natural gas, a combustion (CO

2

) reading must be taken by a qualified technician using properly 

functioning and calibrated combustion analyzing equipment and the results compared to the values in Table 1.

Natural Gas

High Fire with front cover open

Low Fire with front cover open

Max. CO

2

 value

10.1%

Actual Value at High Fire 

Min. CO

2

 value

9.1%

9.1%

Table 1 

- CO

2

 values at High and Low Fire