ibaW-750
Manual
Issue 1.1
19
Figure 6:
Connection via integrated switch
ibaPDA automatically detects the ibaW-750 device and the connected modules if ibaW-
750 and the ibaPDA computer are in the same network (LAN).
The sampling rate can be freely adjusted from 1 Hz to 1 kHz. The maximum amount of
data that can be transmitted depends on the selected sampling rate.
The following rule applies: the higher the sampling rate, the lower the data volume.
The update time of the signals is also limited by the update rate of the K-bus and the
connected modules with their specific properties.
8.2
Reset to factory settings
The device can only be reset by a hardware reset on the device itself.
8.2.1
Procedure
Move the configuration switch to the
Rst
position, hold it and press the reset button at
the same time. The reset button can be pressed with a suitable object (e.g. ballpoint
pen).
If the reset is successful, the device restarts (blinking status indicators) and you can
release both the reset button and the configuration switch.
Please note that the configuration switch only returns to the
Static
position and that you
should set it to the
Cfg
switch position for user-defined IP settings.
8.2.2
Factory settings
8.2.2.1 Device configuration
Owner:
none
Device name:
ibaW-<last 6 digits of the serial number>
IP address:
192.168.1.1
Subnet mask:
255.255.255.0
Gateway:
0.0.0.0
DHCP:
no
8.2.2.2 Module configuration
A reset deletes the entire module configuration including the owner of this module con-
figuration.