ibaPADU-S-IT-16
Manual
Issue 1.10
67
12.2
Interfaces
Interfaces
ibaNet
3Mbit, 32Mbit, 32Mbit Flex
2x ST Lean connectors, FO (50/125 µm and 62.5/125 µm)
for RX/TX
max. cable length 500 m (32Mbit); 2000 m (3Mbit)
Ethernet
10/100 Mbit/s
USB
2x host, 1x device for service purposes
12.3
Digital inputs
Digital inputs
Number
8
Design
Electrically isolated, protected against reverse polarity,
single ended
Debounce filter, 4 different settings can be chosen
Input signal
Max. input voltage
24 V DC
±60 V permanent
Signal level log. 0
Signal level log. 1
> -6 V; < +6 V
< -10 V; > +10 V
Input current
1 mA, constant
Sampling rate
Up to 40 kHz, can be chosen freely
Delay
Typ. 10 µs
Electrical isolation
Channel-channel
Channel-housing
2.5 kV AC
2.5 kV AC
Connection technology
16-pin connector, connector with cage-clamp terminals
(0.2 mm
2
… 2.5 mm
2
), can be screwed, included in deli-
very