Chapter 6 Field Network, PIO, SIO
6.2
Functional Specifications
6-52
ME0392-4C
[9] SIO type
It is the serial communication feature by the SEL program using Free-to-User Channel No. 1.
The general serial communication or the XSEL serial communication protocol (Format B) using
the SEL languages below
(*)
are available.
The communication type requires settings established in the parameter (I/O Parameter No. 201
bit 12 to 15).
(It is set to the general serial communication on delivery)
Category
Condition Command Operand 1
Operand 2
Output
Function
Timer
Optional
TIMC
Program No.
Prohibited
CP
Standby Canceled
Communication
Optional
OPEN
Channel No.
Prohibited
CP
Channel Open
Optional
CLOS
Channel No.
Prohibited
CC Channel Closed
Optional
READ
Channel No.
Column Number
CC Input from Channel
Optional
TMRW
Lead Time
(Light Timer)
CC REA/WRIT Timeout Setting
Optional
WRIT
Cannel No.
Column Number
CP
Output to Channel
Optional
SCHA
Character
Codes
Prohibited
CP
Determination Character Setting
for Data Sending and Receiving
* It is necessary to have the main application part V1.09 or later.
6.3 Parameter Configuration
ME0392-4C
6-53
6.3 Parameter Configuration
6.3.1 Basic setting
(1) I/O slot
●
Module Type and Communication Setting
1) Setting Check in Used Network
Check in I/O Parameter No 225.
No.
Parameter Name
Input range
Unit
Remarks
225 I/O controller
0H to FFFFFFFFH
Bits 0 to 7: Type of Network I/F Module Control 1
(0H: Not mounted,
1H: CC-Link,
2H: DeviceNet,
3H: PROFIBUS-DP,
4 to 5H: Reserved by the system,
6H: EtherCAT,
7H: EtherNet/IP,
8H: Reserved by the system,
9H: PIO,
AH: PROFINET IO,
B to CH: Reserved by the system,
DH:CC-Link IE Field)
* This parameter is already set at delivery.
2) Node Address and TCP/IP Settings
Set the node address in I/O Parameter No. 226 for CC-Link, CC-Link IE Field, DeviceNet,
EtherCAT and PROFIBUS-DP.
For EtherCAT, set as shown below.
• When having automatic assignment of node address from master: Set 0 (setting at delivery)
• When having fixed assignment of node address: Set 1 to 65,535
No.
Parameter Name
Input range
Unit
Remarks
226
I/O1 Fieldbus Node
Address
0 to 99,999,999
Settable Range
•
At CC-Link: 1 to 64
•
At DeviceNet: 0 to 63
•
At PROFIBUS-DP: 0 to 125
•
At EtherCAT: 0 to 65,535
•
At CC-Link IE: 1 to 120
* Setting establishment not necessary for EtherNet/IP and
PROFINET IO
* The range available for setting should differ depending on the network type to be installed. “60D:
Fieldbus Parameter Error” should occur when a number out of the settable range is indicated.
Summary of Contents for R-unit RSEL
Page 2: ......
Page 5: ...ME0392 4C 2 Quick Start Guide Japanese Only ...
Page 32: ...Actuator Coordinate System Intro 18 ME0392 4C 2 Slider type 3 Table type 0 0 0 0 ...
Page 50: ...Chapter 1 RSEL System 1 4 Installation 1 13 ME0392 4C ...
Page 244: ...Chapter 4 Unit connection Installation and Wiring 4 5 PIO Circuit 4 32 ME0392 4C ...
Page 316: ...Chapter 5 Operation 5 10 ELECYLINDER Operation 5 52 ME0392 4C ...
Page 438: ...Chapter 6 Field Network PIO SIO 6 5 Example of Connectivity Setting 6 120 ME0392 4C ...
Page 532: ...10 6 Servo Gain Adjustment 10 90 10 7 Parameter Configuration Advanced Use 10 93 ...
Page 638: ...Chapter 10 Parameter 10 7 Parameter Configuration Advanced Use 10 106 ME0392 4C ...
Page 838: ...Chapter 14 Warranty 14 Warranty 14 3 ME0392 4C ...
Page 843: ......
Page 844: ......